the auto arming sequence and transmit such cancelation to the signal receiving center with the
identification of the authorized user that canceled the action.

The following options must be enabled in the Protege system when using the Auto Arming feature. When
the defer warning time is programmed to 10 minutes, the output group will be activated 10 minutes before
the system performs the Auto Arming in the associated Area.

-

The

Defer Output or Output Group

must be programmed. Refer to the section

Areas | Outputs

in the

Operator Reference Manual for programming instructions.

-

The

Defer Warning Time

must be programmed to not less than 10 minutes. Refer to the section

Areas |

Configuration

in the Operator Reference Manual.

-

The

Defer Automatic Arming

option must be enabled. Refer to the section

Areas | Options (2)

in the

Operator Reference Manual.

Arming Signal

A bell or visual indicator used as an arming acknowledgment signal must be listed to a ULC security,
signaling or fire standard. If intended to be mounted outside, it must be rated for outdoor use.

Double EOL Input Configuration

Only double EOL Input Configuration shall be used. Refer to the

Inputs

section of this manual and the

section

Inputs | Options

in the Operator Reference Manual.

Multiplex System and Poll Time

The Protege controller is compatible with the ArmorIP Internet Monitoring Receiver. Poll Time must be set
to 40 seconds and the Grace Time must be set to 20 seconds.

In the Protege system, the reporting service must be configured to 40 seconds. The following options are
required for the service selected as Report IP type:

-

The

Log Polling Message

option must be enabled. Refer to the section

Report IP | Options

in the

Operator Reference Manual.

-

The

Poll Time

must be programmed to 40 seconds. Refer to the

Report IP | General

section in the

Operator Reference Manual.

Central Station Signal Receiver

The common equipment of each signal receiving center control unit shall be limited to 1000 alarm systems.

Number of attempts

In the event of unsuccessful communication, a digital alarm communicator transmitter shall make a minimum
of 5 and a maximum of 10 attempts. Where the maximum number of attempts to complete the sequence is
reached, an indication of the failure shall be made at the premises.

In the Protege system, the reporting service selected as Contact ID must have the number of attempts
programmed to 5 attempts. The

Dial Attempts

option must be programmed. Refer to the section

Contact

ID | Settings

in the Operator Reference Manual.

Check-In Time

DACT communication channel check-in time is not to exceed 24 hrs.

Trouble Input Service Test Report

-

The

Test Report Time

must be programmed. Refer to the section

Controllers | Configuration

in the

Operator Reference Manual.

-

The

Generate Input Restore on Test Input

option must be enabled. Refer to the section

Controller |

Options

in the Operator Reference Manual.

-

The

Test Report Time is Periodic

option must be enabled. Refer to the section

Controller | Options

in

the Operator Reference Manual.

Primary Communication Channel

The first attempt to send a status change signal shall utilize the primary communication channel.

The Report IP and Contact ID services must be programmed and enabled within the Protege system, and
the CID service must be set as the backup service. The following options are required:

-

The

Contact ID Reporting Service

must be enabled and the

Service Mode

must be configured to start

with the operating system.

-

Refer to the section

Contact ID

in the Operator Reference Manual.

PRT-HPX8-DIN | Protege Half DIN Rail 8 Output Expander | Installation Manual

23

Содержание PRT-HPX8-DIN

Страница 1: ...PRT HPX8 DIN Protege Half DIN Rail 8 Output Expander Installation Manual...

Страница 2: ...echanical for any purpose without the express written permission of Integrated Control Technology Limited Designed and manufactured by Integrated Control Technology Limited Protege and the Protege Log...

Страница 3: ...dicator 14 Power Indicator 14 Output Indicators 14 Error Code Indication 15 Error Code Display 15 Mechanical Diagram 16 Mechanical Layout 17 Technical Specifications 18 New Zealand and Australia 19 Eu...

Страница 4: ...Industry Canada Statement 30 Disclaimer and Warranty 31 PRT HPX8 DIN Protege Half DIN Rail 8 Output Expander Installation Manual 4...

Страница 5: ...to be connected to the RS 485 module network Up to 250 modules can be connected to the Protege system in any combination to the network over a distance of up to 900M 3000ft Further span can be achiev...

Страница 6: ...lar Alarm Systems CAN ULC S302 Installation and Classification of Burglar Alarm Systems for Financial and Commercial Premises Safes and Vaults CAN ULC S561 Installation and Services for Fire Signal Re...

Страница 7: ...per wire or wires of the appropriate gauge Earth Ground Connection The DIN rail enclosure and the DIN rail modules must be grounded to a suitable single point earth ground connection in the installati...

Страница 8: ...Link Connection DIN Rail Enclosure DIN Rail Enclosure DIN Rail Enclosure Module Network RS 485 N N NA and NB DIN Rail Ground Connections multiple cabinets in different rooms sectors or buildings Note...

Страница 9: ...wiring It is also recommended that the module is installed in an electrical room communication equipment room secure cabinet or in an accessible area of the ceiling 1 Position the DIN rail module with...

Страница 10: ...ltage to all devices on the RS 485 network Warning The 12V N and N communication input must be supplied from only one point Connections from more than one 12V supply may cause failure or damage to the...

Страница 11: ...n example below shows the control of an external LED indicator 1K5 OHM 12VAUX 0V LED NO C NC RELAY Warning Switching inductive loads that can produce high back EMF voltages or large voltage induced sp...

Страница 12: ...following table details the trouble inputs that are configured in the system and the trouble type and group that they activate Input Number Description Type Group PXxxx 01 07 Reserved None None PXxxx...

Страница 13: ...he product Refer to the Protege system controller installation manual for address programming details The controller has a set limit on the number of modules of each type that it can support When addi...

Страница 14: ...o normal operation Fault Indicator The fault indicator is lit any time the module is operating in non standard mode If the fault indicator is flashing the module requires a firmware update or is in fi...

Страница 15: ...e feature in the controller s web interface 3 Address Too High The module address is above the maximum number available on the system controller To clear this error change the address to one within th...

Страница 16: ...the output expander Status Indicators Output Indicators 12VDC Pass Through Relay Output 8 12VDC Pass Through 12VDC Input Relay Output 1 RS 485 Input Relay Output 7 12VDC Pass Through Relay Output 5 R...

Страница 17: ...ntial details needed to help ensure correct installation and mounting All measurements are shown in millimeters 90 00 78 40 44 68 67 18 4 67 Screw Hole 39 20 39 20 78 40 17 55 35 40 Back Front PRT HPX...

Страница 18: ...age Temperature 10 to 85 C 14 to 185 F Humidity 0 93 non condensing indoor use only relative humidity Mean Time Between Failures MTBF 587 177 hours calculated using RFD 2000 UTE C 80 810 Standard The...

Страница 19: ...General Product Statement The RCM compliance label indicates that the supplier of the device asserts that it complies with all applicable standards PRT HPX8 DIN Protege Half DIN Rail 8 Output Expande...

Страница 20: ...d otherwise arise from inappropriate waste handling Please contact your local authority for further details of your nearest designated collection point Penalties may be applicable for incorrect dispos...

Страница 21: ...give fail safe operation in the event of a power loss Indication of detection is provided by a LED situated on the front cover The vibration sensor is fully protected from tampering by a N C micro swi...

Страница 22: ...lation Listings EN DIN 12 UL294 UL1076 ULC ORD C1076 86 CAN ULC S319 EN DIN 31 EN DIN 24 EN DIN 24 ATTACK P UL ULC All cabinet installations of this type must be located inside the Protected Area Not...

Страница 23: ...Reference Manual The Poll Time must be programmed to 40 seconds Refer to the Report IP General section in the Operator Reference Manual Central Station Signal Receiver The common equipment of each si...

Страница 24: ...ice attacks Ethernet Connections All ethernet network connections shall be installed within the same room as the equipment Encryption For active communications channel security encryption shall be ena...

Страница 25: ...al Station Receiving software must have the Contact ID details as specified programmed for the Compromise Attempt event Power Supply Mains Power Connection If a flexible cord is used to connect to lin...

Страница 26: ...act ID in the Operator Reference Manual The Report IP Service must be enabled as the primary communication channel the Service Mode must be configured to start with the operating system and the Report...

Страница 27: ...or UL and ULC installations the Central Station Receiving software must have the Contact ID details as specified programmed for the Compromise Attempt event If a flexible cord is used to connect to li...

Страница 28: ...ord is used to connect to line voltage strain relief must be provided for the cord inside the enclosure or at the knockout The power supply is not intended to be mounted on the exterior of vault safe...

Страница 29: ...is device may not cause harmful interference This device must accept any interference received including interference that may cause undesired operation NOTE THE GRANTEE IS NOT RESPONSIBLE FOR ANY CHA...

Страница 30: ...ICES 003 This is a Class A digital device that meets all requirements of the Canadian Interference Causing Equipment Regulations CAN ICES 3 A NMB 3 A PRT HPX8 DIN Protege Half DIN Rail 8 Output Expand...

Страница 31: ...be liable under any circumstances to any party in respect of decisions or actions they may make as a result of using this information In accordance with the ICT policy of enhanced development design...

Страница 32: ...eserved Disclaimer Whilst every effort has been made to ensure accuracy in the representation of this product neither Integrated Control Technology Ltd nor its employees shall be liable under any circ...

Отзывы: