UL and ULC Installation Requirements
Only UL / ULC listed compatible products are intended to be connected to a UL / ULC listed control system.
UL/ULC Installation Cabinet Options
ULC Central Station Fire Monitoring, UL/ULC Central Station Alarm Installations
Cabinet Model
UL/ULC Installation Listings
EN-DIN-24-ATTACK
UL1610, UL1635, UL1076, ULC-S304, ULC-S559
ULC Fire Monitoring
Cabinet Model
ULC Installation Listings
EN-DIN-11V
ULC-S559
EN-DIN-12
EN-DIN-31
EN-DIN-24
EN-DIN-24-ATTACK
Electronic Access Control System Installations
Cabinet Model
UL/ULC Installation Listings
EN-DIN-12
UL294, UL1076, ULC-ORD-C1076-86, CAN/ULC-S319
EN-DIN-31
EN-DIN-24
EN-DIN-24-ATTACK
P
UL
ULC
All cabinet installations of this type must be located
inside the Protected Area
.
Not
to be mounted on the exterior of a vault, safe or stockroom.
All cabinet internal covers and lids/doors must be connected to the cabinet's main ground point for electrical
safety and static discharge protection.
ULC Compliance Requirements
CAN/ULC-S304
⦁
Auto Arming
Control units that support auto arming shall provide an audible signal throughout the protected area not
less than 10 min prior to the auto arming taking place. The control unit shall allow authorized users to cancel
PRT-HPX8-DIN | Protege Half DIN Rail 8 Output Expander | Installation Manual