Battery Indicator

The Battery indicator shows the status of the backup battery.

State

Description (with mains power connected - power indicator on)

Flashing (red)

Backup battery is disconnected

On (red)

Backup battery failed its dynamic battery test

On (green)

Last backup battery dynamic test successful

State

Description (with mains power disconnected - power indicator off)

Flashing (red)

Mains has failed and the PSU is drawing power from the battery. State is Battery Low

Flashing (green) Mains has failed and the PSU is drawing power from the battery. State is Battery Restore

Temp Indicator

The Temp indicator shows the status of the unit's core temperature.

State

Description

On (red)

Core temperature exceeded.

Over Temp Shutdown Activated

Flashing (red)

Core temperature within 10°C of Over Temp Shutdown

On (green)

Core temperature OK

Output Current Indicator

The Output Current indicator shows the status of the output current for both V1+ and V2+.

State

Description

Constantly on

Output current exceeded.

Over Current Shutdown Activated

Continuous flash

Output current exceeded maximum, approaching Over Current Shutdown

Constantly on (all indicators)

Maximum output current level reached

Constantly on (partial)

Indicated output current level reached

PRT-PSU-DIN-8A | Protege DIN Rail 8A Intelligent Power Supply | Installation Manual

25

Содержание Protege PRT-PSU-DIN-8A

Страница 1: ...PRT PSU DIN 8A Protege DIN Rail 8A Intelligent Power Supply Installation Manual ...

Страница 2: ...anical for any purpose without the express written permission of Integrated Control Technology Limited Designed and manufactured by Integrated Control Technology Limited Protege and the Protege Logo are registered trademarks of Integrated Control Technology Limited All other brand or product names are trademarks or registered trademarks of their respective holders Copyright Integrated Control Tech...

Страница 3: ...ng 16 End of Line EOL Resistors 16 Output Load Connection 17 Output Current Influence on Output Load Operation 18 Core Temperature on Output Load Operation 18 Inputs 19 Trouble Inputs 19 Outputs 20 Online Mode 20 Programmable Outputs 20 Offline Mode 20 AC Fail Status Output 20 Battery Fail Status Output 21 Intelligent Monitoring 22 Monitoring Setup 22 Address Configuration 23 PRT PSU DIN 8A Proteg...

Страница 4: ... Current Indicator 25 Error Code Indication 26 Error Code Display 26 Mechanical Diagram 27 Mechanical Layout 28 Technical Specifications 29 New Zealand and Australia 30 European Standards 31 FCC Compliance Statements 33 Industry Canada Statement 34 Disclaimer and Warranty 35 PRT PSU DIN 8A Protege DIN Rail 8A Intelligent Power Supply Installation Manual 4 ...

Страница 5: ... Up to 250 modules can be connected to the Protege system in any combination to the network over a distance of up to 900M 3000ft Further span can be achieved with the use of a network repeater module Locking a network prevents the removal substitution or addition of modules to the module network effectively preventing any tampering with the system The current features of the Power Supply include I...

Страница 6: ...t is to be installed in accordance with The product installation instructions AS NZS 2201 1 Intruder alarm systems The Local Authority Having Jurisdiction AHJ PRT PSU DIN 8A Protege DIN Rail 8A Intelligent Power Supply Installation Manual 6 ...

Страница 7: ...er wire or wires of the appropriate gauge Earth Ground Connection The DIN Rail enclosure and the DIN Rail modules must be grounded to a suitable single point earth ground connection in the installation A minimum 14AWG solid copper wire or thicker in accordance to local authorities shall be used from the Protege system s earth connection points The DIN Rail enclosure includes an earth ground single...

Страница 8: ...ink Connection DIN Rail Enclosure DIN Rail Enclosure DIN Rail Enclosure Module Network RS 485 N N NA and NB DIN Rail Ground Connections multiple cabinets in different rooms sectors or buildings Note that the DIN Rail enclosure earth terminal is connected to the power supply V terminal There must be only one single earth grounding point per system PRT PSU DIN 8A Protege DIN Rail 8A Intelligent Powe...

Страница 9: ... until the tab clips over the rail Removal A Protege DIN Rail module can be removed from the DIN Rail mount using the following steps 1 Insert a flat blade screwdriver into the hole in the module tab clip 2 Lever the tab outwards and rotate the unit off the DIN Rail mount Cabinet Tamper Switch The enclosure tamper input notifies the monitoring station or remote computer that the enclosure has been...

Страница 10: ...nsor mounted within the system enclosure Connection Terminals 1 V and 2 V 12V power connection reverse polarity protected Terminals 3 and 4 N C Alarm output contacts with built in 10 ohm resistor in series PRT PSU DIN 8A Protege DIN Rail 8A Intelligent Power Supply Installation Manual 10 ...

Страница 11: ... adjustment in the high sensitivity area and when in the Off position allows adjustment in the low sensitivity area Installation Procedure 1 Select the intended position for installation ideally positioned horizontally in the vertical center of the enclosure 50mm to the right of the large opening ensuring the surface is clean and clear of any irregularities 2 Remove the sensor cover by unscrewing ...

Страница 12: ... amount turn sensitivity control anti clockwise and bang or tap the protected area Repeat this process until the unit only just responds to the desired impact 11 Replace the sensor cover tighten the fixing screw and check its response to the desired impact PRT PSU DIN 8A Protege DIN Rail 8A Intelligent Power Supply Installation Manual 12 ...

Страница 13: ...on should be made by qualified service personnel and should conform to all local codes Termination of wiring to the Power Supply while power is applied or the battery is connected may cause serious damage to the Power Supply and will VOID ALL WARRANTIES OR GUARANTEES Power the unit only after all wiring configuration and jumper settings are completed Extra care must be taken when wiring the AC inp...

Страница 14: ...rious damage to the Power Supply and will VOID ALL WARRANTIES OR GUARANTEES The battery test procedure uses a special algorithm to prevent deep discharge and increase battery endurance A dynamic battery test is performed every ten minutes when mains power is present and a battery condition alarm will be generated if the battery is either disconnected or shows poor capacity Battery fault conditions...

Страница 15: ...om the Controller or previous module Standard Communications Connection Always connect the Power Supply NA and NB terminals to the NA and NB terminals of the communication network NA N N NB NA N N NB Next module on network Controller or module supplying power to networked devices AUX power from module or external power supply NA N N NB AUX Z1 COM COM Z2 Z3 Z4 Network Power Supplied byNetwork Modul...

Страница 16: ...pedance of 120ohm Maximum total length of cable is 900m 3000ft CAT5e CAT6 are also supported for data transmission when using ground in the same cable to a maximum length of 100m 328ft Warning Unused wires in the cable must not be used to carry power to other devices End of Line EOL Resistors The 330 Ohm EOL End of Line resistor provided in the accessory bag MUST be inserted between the NA and NB ...

Страница 17: ...tputs need to be connected together in parallel When any inductive load including electric locking devices is powered directly or indirectly by the Power Supply a reverse EMF protection diode must be placed across the positive V1 or V2 and negative V terminals at the device 12VDC Electric Locking Device V1 V V1 V1 V1 V1 V1 V V V V V IN4007 Diode Note The 1N4007 diode shown MUST be installed across...

Страница 18: ...urrent Failure Trouble Input Activated Over Current Output Shutdown Activated Core Temperature on Output Load Operation The table below helps illustrate how the core temperature of the power supply module influences the operation of the V1 and V2 outputs Core Temperature Output Load Operation Status 70 C 70 80 C 80 C Outputs Enabled Mains Power Outputs Supplied by Battery Output Over Current Failu...

Страница 19: ...Battery Battery Failure Power Fault General AExxx 04 Output Voltage Low Power Fault General AExxx 05 Output Over Current Failure Power Fault General AExxx 06 Core Temperature Over Temp Failure Power Fault General AExxx 07 Reserved None None AExxx 08 Module Offline Module Offline System Replace xxx with the appropriate address of the module that you are programming The Power Supply emulates an Anal...

Страница 20: ...duced spikes can cause the module to behave unexpectedly and should be avoided A suitable isolation circuit must be installed between the relay contacts of the module and the inductive load These outputs are rated for low power use only 50mA 12V Max Incorrect use may cause erroneous faults or serious damage to the Power Supply and will VOID ALL WARRANTIES OR GUARANTEES Offline Mode Until connectio...

Страница 21: ...tery power without AC power and the backup battery voltage drops below 11 75V Upon reconnecting a backup battery with a voltage greater than 12 5V the output relay will revert back to its default state Normally Closed Ensure common ground between devices Input Expander Power Supply C NC C NC TP V Z1 V Z2 Z3 C Z4 C This output is suited for connection to an input on the Protege System for early det...

Страница 22: ...r Supply will register with the Protege Controller as an Analog Expander module AExxx The channels for each Power Supply will monitor Channel 1 Voltage at V2 output Channel 2 Voltage at V1 output Channel 3 Power Supply module core voltage Channel 4 Total current output The Log Channel Data option may also be selected to view the raw data as it is received in the event log However this will create ...

Страница 23: ...re entry of the module serial number The serial number can be found on the identification sticker on the product Refer to the Protege System Controller installation manual for address programming details PRT PSU DIN 8A Protege DIN Rail 8A Intelligent Power Supply Installation Manual 23 ...

Страница 24: ... Fault Indicator The fault indicator is lit any time the module is operating in non standard mode If the fault indicator is flashing the module requires a firmware update or is in firmware update mode When the fault indicator is on the Status indicator will flash an error code State Description Continuous slow flash red Module is in boot mode awaiting firmware update Constantly on red Module is in...

Страница 25: ...Restore Temp Indicator The Temp indicator shows the status of the unit s core temperature State Description On red Core temperature exceeded Over Temp Shutdown Activated Flashing red Core temperature within 10 C of Over Temp Shutdown On green Core temperature OK Output Current Indicator The Output Current indicator shows the status of the output current for both V1 and V2 State Description Constan...

Страница 26: ...odule update application 3 Address Too High The module address is above the maximum number available on the system controller To clear this error change the address to one within the range set on the system controller restart the module by disconnecting the power 4 Address In Use The Address is already in use by another module To clear this error set the address to one that is not currently occupi...

Страница 27: ...am The mechanical diagram shown below outlines the essential details needed to help ensure the correct installation of the Power Supply PRT PSU DIN 8A Protege DIN Rail 8A Intelligent Power Supply Installation Manual 27 ...

Страница 28: ...elow outlines the essential details needed to help ensure the correct installation of the Power Supply 156 8m m 143 5m m 36 4m m 90mm 90mm 156 8mm FRONT 44 1m m BACK PRT PSU DIN 8A Protege DIN Rail 8A Intelligent Power Supply Installation Manual 28 ...

Страница 29: ...put Trouble Inputs 8 internal Dimensions Dimensions L x W x H 156 8 x 90 x 60mm 6 17 x 3 54 x 2 36 Weight 434g 15 33oz Operating Conditions Operating Temperature 10 to 55 C 14 to 131 F Storage Temperature 10 to 85 C 14 to 185 F Humidity 0 93 non condensing indoor use only relative humidity Mean Time Between Failures MTBF 217 030 hours calculated using RFD 2000 UTE C 80 810 Standard It is important...

Страница 30: ...eneral Product Statement The RCM compliance label indicates that the supplier of the device asserts that it complies with all applicable standards PRT PSU DIN 8A Protege DIN Rail 8A Intelligent Power Supply Installation Manual 30 ...

Страница 31: ...er details of your nearest designated collection point Penalties may be applicable for incorrect disposal of this waste in accordance with your national legislation For business users in the European Union If you wish to discard electrical and electronic equipment please contact your dealer or supplier for further information Information on Disposal in other Countries outside the European Union Th...

Страница 32: ...m of 1 second on detection of an alarm connected in series with the 24Hr tamper input TP on the PSU or any other system input designated programmed as a 24Hr Tamper Alarm This relay is normally energized to give fail safe operation in the event of a power loss Indication of detection is provided by a LED situated on the front cover The vibration sensor is fully protected from tampering by a N C mi...

Страница 33: ...device may not cause harmful interference This device must accept any interference received including interference that may cause undesired operation NOTE THE GRANTEE IS NOT RESPONSIBLE FOR ANY CHANGES OR MODIFICATIONS NOT EXPRESSLY APPROVED BY THE PARTY RESPONSIBLE FOR COMPLIANCE SUCH MODIFICATIONS COULD VOID THE USER S AUTHORITY TO OPERATE THE EQUIPMENT PRT PSU DIN 8A Protege DIN Rail 8A Intelli...

Страница 34: ...ES 003 This is a Class A digital device that meets all requirements of the Canadian Interference Causing Equipment Regulations CAN ICES 3 A NMB 3 A PRT PSU DIN 8A Protege DIN Rail 8A Intelligent Power Supply Installation Manual 34 ...

Страница 35: ...e liable under any circumstances to any party in respect of decisions or actions they may make as a result of using this information In accordance with the ICT policy of enhanced development design and specifications are subject to change without notice For warranty information see our Standard Product Warranty PRT PSU DIN 8A Protege DIN Rail 8A Intelligent Power Supply Installation Manual 35 ...

Страница 36: ...signers manufacturers of integrated electronic access control security and automation products Designed manufactured by Integrated Control Technology Ltd Copyright Integrated Control Technology Limited 2003 2020 All rights reserved Disclaimer Whilst every effort has been made to ensure accuracy in the representation of this product neither Integrated Control Technology Ltd nor its employees shall ...

Отзывы: