To access the inverter through a secure HTTPS connection, use
https://
at
the start of the units URL. (e.g.
https://192.168.0.180:8888
for IP address
192.168.0.180
, HTTPS port
8888
)
UDP Port
: This port is used when applying firmware upgrades to the
inverter. The default UDP port is
9393
.
SNMP:
Configure these settings if you would like to use SNMP based monitoring. SNMP
(Simple Network Management Protocol) is an industry standard protocol for
network management software. Enabling the SNMP function on the inverter will
allow standard SNMP management software to connect to the SNMP agent
running on the inverter and read real time system information such as battery
voltage, and output power. The inverter can send SNMP traps to the external
management software when an alarm or fault occurs.
The information available from the SNMP agent is described in a MIB
(Management Information Base) file, which can be downloaded from the
inverter’s
Help
page. The unique inverter MIB file must then be imported into
your external SNMP management software.
Enable SNMP
: Check this box to enable the SNMP agent
Read Community
: Enter the community string/password for read-only SNMP
access. The default read community string is “public”.
Trap Community
: Assign the community string/password that will be sent
with all traps. Some trap receivers are able to filter based on Trap
Community. The default trap community string is “public”.
Trap IP Addresses
: Assign the IP address for up to two devices that will
receive SNMP traps from the inverter.
Enable SNMP Write Access:
Check this box to allow remote SNMP control of
the inverter output. If this box is unchecked information from the unit will be
read-only.
Write Community
: Enter the community string/password for read-write
SNMP access. The default write community is “write”.
NOTE:
The community strings should be changed to unique passwords before
enabling SNMP, as the defaults are well known.