Load-Shedding is activated

: Check this box to receive an e-mail notification 

when any of the outputs are disabled or enabled due the voltage crossing 
one of the load-shed settings configured on the 

Output Setup

 page. 

 

The Network Watchdog triggers

: Check this box to receive an e-mail 

notification after the Network Watchdog triggers due to a loss of the 
network connection and the network has comes back online. 

 

Alarm Setup 

Use this page to configure the set points of alarms to be monitored, and set the 
required actions when an alarm is triggered. Click on the 

Save Settings

 button at 

the bottom of the page to save any changes. 

 

Fuse Alarm: 

Activate Alarm Form-C Contact

: Checking this box will cause the Alarm relay 

to trigger when an output fuse is blown. 
 

Send E-mail

: Check this box to cause an e-mail notification to be sent when 

an output fuse is blown. Note that the e-mail settings must be fully 
configured on the 

E-mail Setup 

page for this to occur. 

 

System Under Voltage Alarm: 

Under-Voltage Threshold: 

If the system voltage drops below the value in 

this field, the system under-voltage alarm will trigger. 
 

Under-Voltage Recovery:

 If the system voltage rises above the value in this 

field, the system under-voltage alarm will clear. The value in this field must 
be at least 0.50V higher than the Under-Voltage Threshold. 
 

Activate Form-C Contact

: Checking this box will cause the Alarm relay to 

trigger for an under-voltage condition. 
 

Send E-mail

: Checking this box will cause the unit to send a System Under-

Voltage alarm e-mail to the assigned address entered on the 

E-mail Setup

 

page. 

 

System Over Voltage Alarm: 

Over-Voltage Threshold: 

If the system voltage rises above the value in this 

field, the system over-voltage alarm will trigger. 
 

Activate Form-C Contact

: Checking this box will cause the Alarm relay to 

trigger for an over voltage condition. 
 

Содержание DIN Series

Страница 1: ...Innovative Circuit Technology Ltd ICT DIN SERIES POWER DISTRIBUTION UNIT INSTRUCTION MANUAL 855 353 000 Model ICT DIN PDU6...

Страница 2: ...nnect power and allow to cool before removing or replacing Wiring terminals may be HOT to touch Disconnect power and allow to cool before disconnecting load wires Install unit in a restricted access l...

Страница 3: ...WEB BASED INTERFACE 8 Status Control 10 Alarm Status 10 Power Supply 10 Device Setup 11 Output Setup 13 Network Setup 15 E mail Setup 19 Alarm Setup 20 User Setup 21 Maintenance 22 MOBILE WEB APP 23...

Страница 4: ...d alarm input status can be monitored through Ethernet communication Fuse status is also displayed by an LED indicator located over each fuse Form C alarm contacts C NO NC are provided on the top of t...

Страница 5: ...se on the front of the PDU for each output terminal block The fuse number on the front of the PDU matches the output terminal block number Consult your local electrical codes for wire ampacity and fus...

Страница 6: ...Depending on the alarm circuit refer to table 2 connect it between normally open NO and common C between normally closed NC and common C or both The built in web server controls this alarm The alarm c...

Страница 7: ...current is above the set value Alarm Input 1 4 Activate Alarm Form C Contact is checked Digital Alarm is triggered Output Over Current Alarm 1 6 Activate Alarm Form C Contact is checked Output Current...

Страница 8: ...emote monitoring and control using any standard web browser such as Microsoft Edge Google Chrome or Mozilla Firefox To connect with your networked PDU do the following 1 Start Your Browser 2 Enter the...

Страница 9: ...the various monitoring configuration and control features available through the PDU s graphical web interface To log out click on the Logout link on the top right of your browser window The system wi...

Страница 10: ...er to individual outputs If the COMM port on the PDU is connected to an ICT DIN Power Supply this page will also display Power Supply status information including output voltage output current alarm s...

Страница 11: ...ischarges to this level for at least 3s Reconnect Voltage Set the battery reconnect voltage to a level at least 2 0V more than the disconnect voltage to prevent the LVD contactor repeatedly cycling on...

Страница 12: ...abled in sequence when the Enable All Outputs button is pressed on the Status Control page rather than enabling all outputs simultaneously This delay helps prevent power surges that can occur when too...

Страница 13: ...1 to 80 minutes that the remote IP address must stop responding to ping requests from the PDU before the Network Watchdog will trigger an output power cycle Ensure this time is greater than the normal...

Страница 14: ...ter the PDU starts up after a power failure or reset Ignore Fuse Status Will mask the fuse open circuit detection to prevent false alarms on unused channels Enable Power Cycling Check this box to enab...

Страница 15: ...least 5s will trigger the Over Current Alarm Disable this alarm by setting the threshold to 0A Activate Form C Contact Checking this box will cause the Alarm relay to trigger for an over current condi...

Страница 16: ...DU The following ports may be changed within a range of 1 to 65565 if required HTTP Port This port is used for HTTP traffic between the PDU and your browser The default HTTP port is 80 and if you chan...

Страница 17: ...through SNMP If this box is unchecked all information available from the SNMP agent will be read only SNMP Control Access Sets the level of device control that is allowed through SNMP This setting is...

Страница 18: ...or the selected SNMP version will need to be configured Trap Community Assign the community string password that will be sent with all SNMPv1 traps Some trap receivers are able to filter based on Trap...

Страница 19: ...es that are to receive all e mail notifications from the PDU Use commas to separate multiple addresses This field can also be used to send a text message notification to a phone see the Text Message A...

Страница 20: ...otification to be sent when an output fuse is blown Note that the e mail settings must be fully configured on the E mail Setup page for this to occur System Under Voltage Alarm Under Voltage Threshold...

Страница 21: ...front PDU alarm messages Contact Type Select if the external alarm contact input is to be used and what contact type is connected to each input Choose Normally Open contact Normally Closed contact or...

Страница 22: ...gs Maintenance Use this page to reset the PDU soft reset restore the PDU default settings or send a test e mail to verify e mail functionality Reset Distribution Panel Clicking the Reset button will r...

Страница 23: ...Ping Diagnostics Tool Use this feature to verify connectivity of any network connected device Enter the hostname or IP address of the target device and then click the Ping button MOBILE WEB APP Use t...

Страница 24: ...the standard User password and other settings are not affected 1 Press and hold the recessed reset button on the front panel for approximately 10 seconds 2 Release the button 3 Log in to the unit as u...

Страница 25: ...rt you must change the HTTP port the PDU uses from 80 to something else such as 8000 Valid port numbers are in the range of 1 to 65535 See the Network Setup section for information on assigning new ne...

Страница 26: ...port 8000 Figure 7 PDU Access With Router Address TEXT MESSAGE ALARM NOTIFICATIONS The PDU can send alarm notifications as text messages to a cell phone by configuring the alarm e mails to be sent to...

Страница 27: ...section See the Password Reset section for details on how to reset the port number to the factory default value If your network switch allows you to manually configure port speed and duplex settings...

Страница 28: ...d outputs does not exceed the system current rating NOTE Most fuses should be continuously operated at no more than 80 of their nominal current rating Consult the fuse manufacturers specifications Pow...

Страница 29: ...Innovative Circuit Technology Ltd 29 Warranty 2 years Dimensions L x W x H 4 4 x 5 3 x 5 7 111mm x 134mm x 144mm Figure 8 Mechanical Dimensions...

Страница 30: ...such damage Product that is returned as defective which is determined to operate within published specifications will be returned to the Purchaser freight collect ICT assigns to Purchaser any warranti...

Отзывы: