Load-Shedding is activated
: Check this box to receive an e-mail notification
when any of the outputs are disabled or enabled due the voltage crossing
one of the load-shed settings configured on the
Output Setup
page.
The Network Watchdog triggers
: Check this box to receive an e-mail
notification after the Network Watchdog triggers due to a loss of the
network connection and the network has comes back online.
Alarm Setup
Use this page to configure the set points of alarms to be monitored, and set the
required actions when an alarm is triggered. Click on the
Save Settings
button at
the bottom of the page to save any changes.
Fuse Alarm:
Activate Alarm Form-C Contact
: Checking this box will cause the Alarm relay
to trigger when an output fuse is blown.
Send E-mail
: Check this box to cause an e-mail notification to be sent when
an output fuse is blown. Note that the e-mail settings must be fully
configured on the
E-mail Setup
page for this to occur.
System Under Voltage Alarm:
Under-Voltage Threshold:
If the system voltage drops below the value in
this field, the system under-voltage alarm will trigger.
Under-Voltage Recovery:
If the system voltage rises above the value in this
field, the system under-voltage alarm will clear. The value in this field must
be at least 0.50V higher than the Under-Voltage Threshold.
Activate Form-C Contact
: Checking this box will cause the Alarm relay to
trigger for an under-voltage condition.
Send E-mail
: Checking this box will cause the unit to send a System Under-
Voltage alarm e-mail to the assigned address entered on the
E-mail Setup
page.
System Over Voltage Alarm:
Over-Voltage Threshold:
If the system voltage rises above the value in this
field, the system over-voltage alarm will trigger.
Activate Form-C Contact
: Checking this box will cause the Alarm relay to
trigger for an over voltage condition.