is useful for re-booting a modem or other network device that is powered by 
one of the PDU outputs, to help recover the network IP connection when 
one of these devices has crashed. A delay time must be entered in the 

Sequence/Cycle Delay

 field for this function to work. Power for a cycled 

channel will be held in the off state for the duration set by the 
Sequence/Cycle delay time, then will be turned back on. 

 

Watchdog Enabled

:  Check this box to enable the selected Watchdog. 

 

Primary IP Address

: Enter the remote IP address you would like the selected 

Watchdog to monitor. If left blank the unit will monitor the Gateway IP 
address listed in the Network Setup page. 

 

Secondary IP Address

: Enter an optional second IP address that the unit can 

monitor to verify network status. The Network Watchdog will only trigger if 
both the Primary and Secondary IP addresses fail to respond. 
 

Cycle Outputs

: This sets which output(s) to power cycle when the Network 

Watchdog triggers. 
 

Watchdog Timeout

: Enter the time (1 to 80 minutes) that the remote IP 

address must stop responding to ping requests from the PDU, before the 
Network Watchdog will trigger an output power cycle. Ensure this time is 
greater than the normal start-up time for the network hardware to prevent 
nuisance power cycle events at system start up. 
 

Maximum Cycle Attempts:

 This setting will limit the maximum number of 

times the PDU can attempt to cycle power to the output(s) before giving up, 
if the remote IP address continues to be unresponsive. Set Maximum Cycle 
Attempts to zero for no limit. 

 

Data Logging: 

Data Logging rate: 

Enable this feature to keep a running record the system 

voltage, system current, channel output currents, fuse status, and alarm 
inputs at a rate of up to 1 sample per minute. View this Comma Separated 
Values (CSV) format log by clicking the 

Download Log

 button, and open in 

any Spreadsheet software, such as Microsoft Excel. The log will store up to 
30days of data, with the oldest entries at the top of the file, newest at the 
bottom. 
 

Log Start Date

: Shows the date/time the most recent log began. 

 

Output Setup 

This page allows you to configure the output settings of the PDU. In the 

Select an 

Output

 

to edit

 box, click on the output number of the output you wish to 

Содержание DIN Series

Страница 1: ...Innovative Circuit Technology Ltd ICT DIN SERIES POWER DISTRIBUTION UNIT INSTRUCTION MANUAL 855 353 000 Model ICT DIN PDU6...

Страница 2: ...nnect power and allow to cool before removing or replacing Wiring terminals may be HOT to touch Disconnect power and allow to cool before disconnecting load wires Install unit in a restricted access l...

Страница 3: ...WEB BASED INTERFACE 8 Status Control 10 Alarm Status 10 Power Supply 10 Device Setup 11 Output Setup 13 Network Setup 15 E mail Setup 19 Alarm Setup 20 User Setup 21 Maintenance 22 MOBILE WEB APP 23...

Страница 4: ...d alarm input status can be monitored through Ethernet communication Fuse status is also displayed by an LED indicator located over each fuse Form C alarm contacts C NO NC are provided on the top of t...

Страница 5: ...se on the front of the PDU for each output terminal block The fuse number on the front of the PDU matches the output terminal block number Consult your local electrical codes for wire ampacity and fus...

Страница 6: ...Depending on the alarm circuit refer to table 2 connect it between normally open NO and common C between normally closed NC and common C or both The built in web server controls this alarm The alarm c...

Страница 7: ...current is above the set value Alarm Input 1 4 Activate Alarm Form C Contact is checked Digital Alarm is triggered Output Over Current Alarm 1 6 Activate Alarm Form C Contact is checked Output Current...

Страница 8: ...emote monitoring and control using any standard web browser such as Microsoft Edge Google Chrome or Mozilla Firefox To connect with your networked PDU do the following 1 Start Your Browser 2 Enter the...

Страница 9: ...the various monitoring configuration and control features available through the PDU s graphical web interface To log out click on the Logout link on the top right of your browser window The system wi...

Страница 10: ...er to individual outputs If the COMM port on the PDU is connected to an ICT DIN Power Supply this page will also display Power Supply status information including output voltage output current alarm s...

Страница 11: ...ischarges to this level for at least 3s Reconnect Voltage Set the battery reconnect voltage to a level at least 2 0V more than the disconnect voltage to prevent the LVD contactor repeatedly cycling on...

Страница 12: ...abled in sequence when the Enable All Outputs button is pressed on the Status Control page rather than enabling all outputs simultaneously This delay helps prevent power surges that can occur when too...

Страница 13: ...1 to 80 minutes that the remote IP address must stop responding to ping requests from the PDU before the Network Watchdog will trigger an output power cycle Ensure this time is greater than the normal...

Страница 14: ...ter the PDU starts up after a power failure or reset Ignore Fuse Status Will mask the fuse open circuit detection to prevent false alarms on unused channels Enable Power Cycling Check this box to enab...

Страница 15: ...least 5s will trigger the Over Current Alarm Disable this alarm by setting the threshold to 0A Activate Form C Contact Checking this box will cause the Alarm relay to trigger for an over current condi...

Страница 16: ...DU The following ports may be changed within a range of 1 to 65565 if required HTTP Port This port is used for HTTP traffic between the PDU and your browser The default HTTP port is 80 and if you chan...

Страница 17: ...through SNMP If this box is unchecked all information available from the SNMP agent will be read only SNMP Control Access Sets the level of device control that is allowed through SNMP This setting is...

Страница 18: ...or the selected SNMP version will need to be configured Trap Community Assign the community string password that will be sent with all SNMPv1 traps Some trap receivers are able to filter based on Trap...

Страница 19: ...es that are to receive all e mail notifications from the PDU Use commas to separate multiple addresses This field can also be used to send a text message notification to a phone see the Text Message A...

Страница 20: ...otification to be sent when an output fuse is blown Note that the e mail settings must be fully configured on the E mail Setup page for this to occur System Under Voltage Alarm Under Voltage Threshold...

Страница 21: ...front PDU alarm messages Contact Type Select if the external alarm contact input is to be used and what contact type is connected to each input Choose Normally Open contact Normally Closed contact or...

Страница 22: ...gs Maintenance Use this page to reset the PDU soft reset restore the PDU default settings or send a test e mail to verify e mail functionality Reset Distribution Panel Clicking the Reset button will r...

Страница 23: ...Ping Diagnostics Tool Use this feature to verify connectivity of any network connected device Enter the hostname or IP address of the target device and then click the Ping button MOBILE WEB APP Use t...

Страница 24: ...the standard User password and other settings are not affected 1 Press and hold the recessed reset button on the front panel for approximately 10 seconds 2 Release the button 3 Log in to the unit as u...

Страница 25: ...rt you must change the HTTP port the PDU uses from 80 to something else such as 8000 Valid port numbers are in the range of 1 to 65535 See the Network Setup section for information on assigning new ne...

Страница 26: ...port 8000 Figure 7 PDU Access With Router Address TEXT MESSAGE ALARM NOTIFICATIONS The PDU can send alarm notifications as text messages to a cell phone by configuring the alarm e mails to be sent to...

Страница 27: ...section See the Password Reset section for details on how to reset the port number to the factory default value If your network switch allows you to manually configure port speed and duplex settings...

Страница 28: ...d outputs does not exceed the system current rating NOTE Most fuses should be continuously operated at no more than 80 of their nominal current rating Consult the fuse manufacturers specifications Pow...

Страница 29: ...Innovative Circuit Technology Ltd 29 Warranty 2 years Dimensions L x W x H 4 4 x 5 3 x 5 7 111mm x 134mm x 144mm Figure 8 Mechanical Dimensions...

Страница 30: ...such damage Product that is returned as defective which is determined to operate within published specifications will be returned to the Purchaser freight collect ICT assigns to Purchaser any warranti...

Отзывы: