Technical features:

• red display of -19999…99999 digits (optional: green, orange or blue display)

• minimal installation depth: 70 mm without plug-in terminal

• min/max memory

• adjustment via factory default or directly on the sensor signal

• 30 adjustable supporting points

• display flashing at threshold undercut or exceedance

• simplified parameterisation U/min with only 3 parameters

• Schmitt-trigger-input

• zero-key for triggering of Hold, Tara

• permanent min/max-value recording

• digital frequency filter for contact bounce suppression and interference suppresion

• frequency filter with varying pulse-duty factor

• volume metering (totaliser) for frequencies up to 1 kHz (accurate to a pulse)

• mathematical function like reciprocal value, square root, rounding

• sliding averaging with an optional dynamic display filter

• setpoint generator

• brightness control

• programming interlock via access code

• protection class IP65 at the front

• plug-in terminal

• sensor supply

• galv. isolated digital input

• option: relay outputs

• option: analog output

• accessories: PC-based configuration-kit PM-TOOL incl. CD & USB-adapter

User manual 

IM2

-1F

Frequency input: 0.01 Hz to 999.99 kHz / 0.01 Hz to 9.9999 kHz / 0-2.500 kHz 

Connection for Namur, NPN/PNP with HTL- or TTL-output or for

position survey via incremental encoder

Содержание IM2-1F

Страница 1: ...rence suppresion frequency filter with varying pulse duty factor volume metering totaliser for frequencies up to 1 kHz accurate to a pulse mathematical function like reciprocal value square root round...

Страница 2: ...oints 0 no switching points Type of display 2 2 relay outputs Frequency F Protection class Display colour 1 without keypad Blue B operation via PM TOOL Green G 7 IP65 plug in terminal Red R Yellow Y V...

Страница 3: ...ent setpoint value function nominal value function averaging brightness control as well as the control of the digital input and keyboard layout 5 4 3 Safety parameters 26 Assignment of user and master...

Страница 4: ...nt the device can be adjusted onto different kind of applications and later on different functions of the device can be controlled The adjustment is also possible via the PC Software PM TOOL with a sp...

Страница 5: ...for physical unit 89 0 1 After removing the fixing elements insert the device 2 Check the seal to make sure it fits securely 3 Click the fixing elements back into place and tighten the clamping screw...

Страница 6: ...R5B 0307 570xD supply of 230 VAC 21 22 23 24 25 26 S1 S2 Options 5 Relay 1 Relay 2 1 2 3 10 11 9 4 5 6 7 8 TTL or Namur Pulse input 1 _ Sensor supply 24 VDC 3 wire sensor 230 VAC or 115 VAC N L Digita...

Страница 7: ...cally connected in the device Type IM2 1FR5B 0007 670xD supply of 10 30 VDC galv isolated 1 2 3 10 11 9 4 5 6 7 8 TTL or Namur Pulse input 1 3 wire sensor 10 30 VDC _ Pulse input 2 TTL or Namur 3 wire...

Страница 8: ...nnection examples with practical applications 10 30 VDC Namur 1 2 3 10 11 9 4 5 6 7 8 IN NAMUR 230 VAC Namur NAMUR IN N L 1 2 3 10 11 9 4 5 6 7 8 10 30 VDC 3 wire PNP IN 3 wire _ 1 2 3 10 11 9 4 5 6 7...

Страница 9: ...wire NPN IN 3 wire N L Pull up extern 2 7 k 0 5 W 1 2 3 10 11 9 4 5 6 7 8 10 30 VDC _ Incremental encoder with analog output 4 20 mA 1 2 3 10 11 9 4 5 6 7 8 Incremental encoder A A B Incremental enco...

Страница 10: ...deposited in the menu item can be parameterised here Functions that can be changed or adjusted are always signalised by a flashing of the display Settings that are made in the parameterisation level...

Страница 11: ...tool the device configuration can be generated omitted and saved on the PC The parameters can be changed via the easy to handle program surface whereat the operating mode and the possible selection op...

Страница 12: ...hes back to menu level Adjustment of pulses per rotation Default This parameter is only important if or has been selected Generally it shows the number of pulses per rotation 5 1 Switching on Once the...

Страница 13: ...input option you can only select between and With only the previously set display value is taken over and with the device takes over both the display value and the analogue input value Setting the sta...

Страница 14: ...to 10 0 sec Confirm the selection by pressing the P button The display then switches back to the menu level again Rescaling the measuring input values Default With this function rescale the input val...

Страница 15: ...d by the adjustment frequencies are ignored by the adjusted frequency filter Act on the assumption that the pulse duty factor is 1 1 Accordingly the minimal pulse duration is derived from the half of...

Страница 16: ...up one after another Hysteresis for limit values Default For all limit values exists a hysteresis function that reacts according to the settings threshold exceedance threshold undercut Function if dis...

Страница 17: ...number combination free available Default If this code is set 0000 all parameters are locked if has been selected before under menu item By pushing P during operation mode for approx 3 seconds appear...

Страница 18: ...ically switches to operating mode If was selected the keyboard is locked To get back into the menu level press P for 3 seconds in operating mode Now enter the works setting that appears using plus P t...

Страница 19: ...referred the final value needs to be entered under and the final frequency needs to be entered under Under the initial value needs to be entered and under the initial frequency There is no application...

Страница 20: ...el If was selected as input option one can only select between and With only the previously set display value is taken over and with the device takes over both the display value and the analogue input...

Страница 21: ...sec Confirm the selection by pressing the P button The display then switches back to the menu level again Rescaling the measuring input values Default With this function you can rescale the input val...

Страница 22: ...he optional filter is not activated by the adjustment frequences are ignored by the adjusted frequency filter Act on the assumption that the pulse duty factor is 1 1 Accordingly the minimal pulse dura...

Страница 23: ...ding to their value At the sensor calibration like at final value offset one is asked at the end if a calibration shall be activated Analog values for setpoints These setpoints are displayed at works...

Страница 24: ...into menu group level 5 4 2 General device parameters Menu level Parameterisation level Display time Default The display is set up with Thereby on switches until 1 second in 0 1 steps and until 10 0 s...

Страница 25: ...to menu level Sliding average determination Default Here the number of the meterings that need to be averaged is preset The time of averaging results of the product of measuring time and the averaged...

Страница 26: ...lue Furthermore it can be used for calculating the difference At this the constant value is substracted from the current measurand and the difference is evaluated in the alerting or by the analog outp...

Страница 27: ...changes into menu level Brightness control Default The brightness of the display can be adjusted in 16 levels from 00 very dark to 15 very bright via this parameter or alternatively via the navigatio...

Страница 28: ...liser can be set back by pressing the navigation keys the device acknowledges this with showing in the display The configuration of deletes the min max memory Under the measurand is shown for approx 7...

Страница 29: ...an output can be set and therewith e g a setpoint adjustment can be done If is selected the O key is without any function in the operation mode Special function digital input Default In operation mod...

Страница 30: ...can be changed from e g 0 20 mA to 4 20 mA or 0 10 VDC At analog output parameters are released At all analog output parameters are locked Release lock alarm parameters Default This parameter describ...

Страница 31: ...f is selected the signal of the analog output will be kept It can be continued processing after a deactivation of With P the selection is confirmed and the device changes into menu level Selection ana...

Страница 32: ...ow behaviour of the analog output can be defined As overflow can be seen either that means the analog output runs on the set limits e g 4 and 20 mA or input value smaller than initial value analog out...

Страница 33: ...play are set not set on the front of the device With P the selection is confirmed and the device changes into menu level Logic relay 1 Default Here the switching behaviour of the relay is defined via...

Страница 34: ...tpoints can be activated deactivated in this case the output and the setpoint display are set not set on the front of the device With P the selection is confirmed and the device changes into menu leve...

Страница 35: ...y of alarm 1 can be related to special functions in detail these are the current measurand the min value the max value the totaliser value sum value the constant value or the difference between the cu...

Страница 36: ...display falls below exceeds limit value Default The limit value undercut can be selected with LOW lower limit value and limit value exceedance can be selected with HIGH upper limit value If e g limit...

Страница 37: ...scaled input signal is integrated by a time and steadily select or temporarily select saved If is selected the function is deactivated With P the selection is confirmed and the device changes into men...

Страница 38: ...et Default The reset value is adjusted from the smallest to the highest digit with the navigation keys and digit per digit confirmed with P After the last digit the display switches back to the menu l...

Страница 39: ...limit value in regard of an undercut or exceedance Each alarm can be allocated to an optional relay output S1 S2 furthermore alarms can be controlled by events like e g hold or min max value Function...

Страница 40: ...switching on delay is activated via an alarm and e g switched 10 seconds after reaching the switching threshold a short term exceedance of the switching value does not cause an alarm respectively doe...

Страница 41: ...ion coverage A measuring system for length works via a incremental encoder with two dephased output signals typically A and B and 100 pulse rotation The axis perimeter was calculated in a way that the...

Страница 42: ...ply never exceeds 10 kHz rather 3 kHz Assume a rotation speed of 60 r p m at 1 Hz whereat the real frequency value will not be considered Our example complies with a number of sprockets of 64 Setting...

Страница 43: ...aft Applied in an angle of 90 to each other and to the rotation speed measurement The sprockets are collected via a proximity switch and evaluated by the frequency device which shall display the rotat...

Страница 44: ...ight 14 mm Segment colour red optional green yellow or blue Range of display 19999 to 99999 Switching points one LED per switching point Overflow horizontal bars at the top Underflow horizontal bars a...

Страница 45: ...change over contacts 250 VAC 5 AAC 30 VDC 5 ADC 30 x 103 at 5 AAC 5 ADC ohm resistive load 10 x 106 mechanically Diversity according to DIN EN50178 Characteristics according to DIN EN60255 Power suppl...

Страница 46: ...olenoid valves etc near the device and suppress any interference with the aid of RC spark extinguishing combinations or free wheeling diodes Keep input output and supply lines separate from one anothe...

Страница 47: ...y with the dynamic function Step The displayed value displ needs to be set on AVG 4 The display remains on zero The sensor was not connected properly Check the connection lines and if necessary the se...

Страница 48: ...ing to your application 6 Program numbers for the parameterisation of the input are not available The programming interlock is activated Enter correct code 7 The device shows Err1 in the 7 segment dis...