ET-7X00/PET-7X00 User Manual, version 1.1.2 Page: 111
Copyright © 2013 ICP DAS CO., LTD. All Rights Reserved. E-mail: [email protected]
4.1 Please double-click the “ModbusMasterToolPC.exe” to open it and click the
“Setup > Definition” in menu bar to setup the parameters.
Modbus Address for Calibration
Register
Points
Description
Access Type
00830
1
Enable/Disable Calibration
0=Disabled
1=Enabled
R/W
00831
1
Zero calibration command of ch0, 1 = run
W (Pulse)
00832
1
Span calibration command of ch0, 1 = run
W (Pulse)
Note:
When calibrating current type (i.e. type 06, 07 and 1A), the jumper of the
corresponding channel should be short.
Refer to the link for details.
ftp://ftp.icpdas.com/pub/cd/6000cd/napdos/et7000_et7200/document/data_she
et/
It depends on the settings in Modules I/O Settings -
Modbus Definition (refer to Section 0)
Select “01 Read Coils Status” (no
matter what kind of module you use).
Rrefer to the table below - Modbus
Address for Calibration. (830 ~ 832)
1.
2.
3.