ICP OCF105A12C Скачать руководство пользователя страница 3

 

 

 

j. 

Before servicing, allow furnace to cool down. Always shut off 
electricity and fuel to furnace when servicing. This will prevent 
electrical shock or burns; 

k. 

Seal supply and return air ducts; 

l. 

The vent system 

MUST

 be checked to determine that it is the 

correct type and size; 

m.  Install correct filter type and size; 

n. Unit 

MUST

 be installed so that electrical components are 

protected from direct contact with water. 

 
 

1.2.1) Safety 

Rules 

 

Your unit is built to provide many years of safe and dependable 
service, provided it is properly installed and maintained. However, 
abuse and/or improper use can shorten the life of the unit and create 
hazards for you, the owner. 
 
a. 

The U.S. Consumer Product Safety Commission recommends 
that users of oil-burning appliances install carbon monoxide 
detectors. There can be various sources of carbon monoxide in a 
building or dwelling. The sources could be gas-fired clothes 
dryers, gas cooking stoves, water heaters, furnaces, gas-fired 
fireplaces, wood fireplaces, and several other items. Carbon 
monoxide can cause serious bodily injury and/or death. 

 

Therefore, to help alert people to potentially dangerous carbon 
monoxide levels, you should have carbon monoxide detectors 
listed by a nationally recognised agency (ex. Underwriters 
Laboratories or International Approval Services) installed and 
maintained in the building or dwelling (see Note below). 

 
b. 

There can be numerous sources of fire or smoke in a building or 
dwelling. Fire or smoke can cause serious bodily injury, death, 
and/or property damage. Therefore, in order to alert people to 
potentially dangerous fire or smoke conditions, you should have 
Underwriters Laboratories listed fire and smoke detectors 
installed and maintained in the building or dwelling (see Note 
below). 

 
 

NOTE:

 The manufacturer of your furnace does not test 

detectors and makes no representations regarding any 
brand or type of detector. 

 
 

CAUTION 

Ensure that the area around the combustion air intake 
terminal is free of snow, ice and debris

 
 

CAUTION 

An air pressure switch MUST be used when the furnace 
is side-wall vented. 

 
 

CAUTION 

Do not use any commercially available soot remover. 
This furnace has a ceramic fibre type of combustion 
chamber. Normal servicing of this unit does not require 
the cleaning of same. Use extreme caution if for any 
reason you have to work in the area of the combustion 
chamber. 

 

1.2.2)  Freezing Temperatures and Your Structure 

 
 

WARNING 

 
Freezing temperature warning. 
 
Turn off water supply. 
 
If your heater remains shut off during cold weather, 
the water pipes could freeze and burst, resulting in 
serious water damage.

 

 
 
Your unit is equipped with safety devices that may keep it from 
operating if sensors detect abnormal conditions such as clogged 
exhaust flues. 
 
If the structure is unattended during cold weather you should take the 
following precautions: 

a. 

Turn off main water supply into the structure and drain the water 
lines if possible. Open faucets in appropriate areas; 

b.  Have someone check the structure frequently during cold 

weather to make sure it is warm enough to prevent pipes from 
freezing. Contact a qualified service agency, if required. 

 
 

1.2.3) Installation 

regulations 

 
All local and national code requirements governing the installation of 
oil burning equipment, wiring and flue connections MUST be followed. 
Some of the codes that may be applicable are:  
 
CSA B139 

INSTALLATION CODE FOR OIL 
BURNING EQUIPMENT 

NFPA 31 

INSTALLATION OF OIL BURNING 
EQUIPMENT 

ANSI/NFPA 90B 

WARM AIR HEATING AND AIR 
CONDITIONING SYSTEMS 

ANSI/NFPA 70 

NATIONAL ELECTRICAL CODE 

CSA C22.1 

CANADIAN ELECTRICAL CODE 

 
Only the latest issues of the above codes should be used. 
 
 

1.3) 

POSITIONING THE FURNACE 

 
 

CAUTION 

Carefully check your furnace upon delivery for any 
evidence of damage that may have occurred during 
shipping and handling. Any claims for damages or lost 
parts must be made with the Transport Company. 

 
 

445 01 4024 05

Содержание OCF105A12C

Страница 1: ...CING OF THE UNIT AND KEEP THE DOCUMENT NEAR THE FURNACE FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE Printed in Canada Printed on 100 recycled paper OIL...

Страница 2: ...s and test instruments Failure to carefully read and follow all instructions in this manual can result in personal injury and or death property damage furnace malfunction WARNING Fire hazard The furna...

Страница 3: ...ions regarding any brand or type of detector CAUTION Ensure that the area around the combustion air intake terminal is free of snow ice and debris CAUTION An air pressure switch MUST be used when the...

Страница 4: ...ine or any other damaging chemicals Refer to Part 1 section 5 2 1 4 VENTING 1 4 1 General The furnaces can be vented in several ways Chimney Vented Using the Beckett AFG or Riello 40 F burner the furn...

Страница 5: ...ected to a 20 foot tall clay lined masonry chimney the thermal resistance of this type of chimney is R2 which is less than R6 The actual firing rate at 156 psig is 1 25 x 60 75 Therefore this table sh...

Страница 6: ...nal in accordance with all local and national codes The following requirements shall be considered to be minimum requirements that can be overridden by stricter local and national codes FIGURE 1 The v...

Страница 7: ...hat the band will close with an action of one strip sliding over the other not under the gear head of the draw clamp see Figure 1 8 Tighten the band clamp with considerable torque to cause the gum sea...

Страница 8: ...E BACK 5 THREAD SPIN SLEEVE BACK 10 CUT STAINLESS STEEL CORE BACK BY 3 9 FIGURE 1 3 FIGURE 1 4 FIGURE 1 1 FIGURE 1 2 FIGURE 1 5 FIGURE 1 6 INSERT STAINLESS STEEL CORE ONTO BREECH TUBE DRIVE THREE STAI...

Страница 9: ...IGURE 1 8 SEALANT FLOWING OUT FROM UNDER BAND CLAMP AT TERMINAL SEALANT OUTFLOW FIGURE 1 11 10 APPLY THE SEALANT TO THE TUBE END SEALANT OUTFLOW SEALANT FLOWING OUT FROM UNDER BAND CLAMP AT BREECH TWI...

Страница 10: ...TIGHTLY INTO RECESS INSTALL STABILIZER SHROUD CAULK TO SEAL STABILIZER SHROUD TO THE WALL FIGURE 1 13 FIGURE 1 14 FIGURE 1 12 VENT TERMINAL PRESSURE SWITCH REFER TO WIRING DIAGRAM FOR ELECTRICAL CONNE...

Страница 11: ...t 1 section 5 3 1 5 3 Outdoor Combustion Air Side wall Venting DV 2000 for a complete description 1 5 AIR FOR COMBUSTION WARNING Poisonous carbon monoxide gas hazard Comply with NFPA standards for the...

Страница 12: ...two plastics Intake pipe length DV 2000 The DV 2000 venting system has been certified for 37 equivalent m 120 equivalent feet of 3 intake pipe Count a 90 elbow as 10 equivalent feet and a 45 elbow as...

Страница 13: ...king Checking the air and turbulator settings Before starting the burner for the first time adjust the air and turbulator settings to those listed in Table 4 Once the burner becomes operational final...

Страница 14: ...e heat exchanger Wire the thermostat and condensing unit contactor as indicated in the wiring diagram Figure 6 1 9 4 Ductwork and Filter Installation Design and install the air distribution system to...

Страница 15: ...Fan Limit Control heats up to the factory set point the circulating air blower starts 7 The circulating air blower and burner motor remain on until the thermostat is satisfied Also the solenoid valve...

Страница 16: ...shut down for an extended period of time 4 Set thermostat higher than the room temperature 5 If the burner motor does not start or ignition fails turn off the disconnect switch and CALL A QUALIFIED SE...

Страница 17: ...flame should shut down before a 1 smoke reading occurs 3 Gradually block the vent outlet The burner flame should shut down before a 1 smoke reading occurs 4 If the burner does not shut down before 1...

Страница 18: ...ly from the front inspection port Also the furnace has external clean out ports so the soot does not fall into the fan compartment during the cleaning operation IMPORTANT Do not vacuum the ceramic cha...

Страница 19: ...een installed the burner will have to be removed to check the retention head 3 1 4 Nozzle Replace the nozzle with the one specified in Table 4 3 1 5 Oil filters Tank filter The tank filter should be r...

Страница 20: ...hone Day Night Dealer name and address START UP TEST RESULTS Nozzle Pressure lbpsi Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Ambient t...

Страница 21: ...3 3 4 5 AFUE From CSA B212 standard and Canadian regulation 81 5 81 0 80 3 AFUE From ASHRAE 103 standard and US regulation 81 5 81 0 80 3 RIELLO BURNER SIDE WALL INSTALLATION Burner tube insertion len...

Страница 22: ...DNS 0589 Rev C FIGURE 5 Models ODH53F100LB 3MC OCF105A12C 23 445 01 4024 05...

Страница 23: ...24 FIGURE 6 Wiring diagram ODH53F100LB 3MC OCF105A12C 445 01 4024 05...

Страница 24: ...COMPONENTS AND REPLACEMENT PARTS 25 445 01 4024 05...

Страница 25: ...PARTS LIST Model ODH53F100LB 3MC OCF105A12C B50030A 26 445 01 4024 05...

Страница 26: ...gonal nut 3 8 16NC brass F07F024 32 Washer panel peep hole B30752 33 Hexagonal flange nut 3 8 16NC brass F07O001 34A 5 breech plate B30459 34B 3 breech plate B30515 35 Gasket breech plate B30415 02 36...

Отзывы: