2.3.7)  Overfire pressure test procedure 

 

1. 

To read the pressure, replace the glass with the washer supplied 
with the appliance; 

2.  After the test, put the glass back in place in the sight glass 

assembly; 

3. 

Verify that the pressure reading corresponds to the one specified 
in Table 4. Also see Figure 3.1. 

 

FIGURE 3.1 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

2.3.8) Fan-Limit 

adjustment 

 
Modification of the “FAN ON” and “HI” limit settings on the Fan-Limit 
can cause malfunctioning of the furnace and result in premature wear 
of the heat exchanger. 
 

CAUTION 

Modification of the factory set limits will void the 
warranty. 

 

2.3.9)  Limit control check 

 
After operating the furnace for at least 15 minutes, restrict the return 
air supply by blocking the filters or the return air register and allow the 
furnace to shut off on High Limit. The burner will shut off but the 
blower will continue to run. 
 
Remove the obstruction and the burner should restart after a few 
minutes. 
 

FIGURE 4

 

 
 
 
 
 
 
 
 
 

 

2.3.10)  DV-2000™ Blocked intake / blocked vent 

test 

 

On side-wall vented furnaces, the DV-2000™ venting system 
incorporates a safety shutdown system that will shut the burner down 
before #1 smoke occurs due to the presence of a blocked intake or 
blocked vent outlet. Test the system as follows: 
 
1. 

Ensure that the furnace has been running for at least 10 minutes; 

2. 

Gradually block the intake. The burner flame should shut down 
before a #1 smoke reading occurs; 

3. 

Gradually block the vent outlet. The burner flame should shut 
down before a #1 smoke reading occurs; 

4. 

If the burner does not shut down before #1 smoke occurs, ensure 
that the burner is set up according to Part 2, section 3.4 (2.3.4). 
Perform the CO

2

/ Smoke Test, and allow for the 1.5% CO

2

 

operating headroom required by the instructions; 

5. 

If the burner still does not shut down before #1 smoke occurs, 
check for a blockage in the pressure hose, or at the hose 
connection points. 

 

IMPORTANT 

The DV-2000™ safety shutdown system will shut down 
the burner flame during a blocked intake or blocked 
vent condition if and only if the burner has been set up 
and calibrated in accordance with Part 2, section 3.4 
(2.3.4). Perform the CO

/ Smoke Test. For instance, if 

the burner is adjusted and final-set to a #1 smoke 
condition during normal operation, the burner flame 
cannot possibly shut down before #1 smoke occurs 
during a blockage condition. 

 
2.3.11)  BVSO performance test 
 

The purpose of the following test is to check that the electrical outlet 
on the furnace, designated to the BVSO, is functional. 
 
1. 

Start up the burner; 

2.  Remove the three-pole plug from the BVSO outlet on the 

furnace; 

3. 

The burner must shut-off immediately, while the blower continues 
to run to the end of the cool-down cycle. 

If the test is not in line with the above, call a QUALIFIED SERVICE 
TECHNICIAN. 

 

 
 
 

 

 
 
 
 
 
 
 
 
 
 
 

DNS-0703 Rev. A

 

18 

DNS-0355 Rev. B 

200˚ F 

Limit ‘’HI’’ 

130˚ F 

Limit ‘’FAN ON’’ 

90˚ F 

Limit ‘’FAN OFF’’ 

 

 

445 01 4024 05

Содержание OCF105A12C

Страница 1: ...CING OF THE UNIT AND KEEP THE DOCUMENT NEAR THE FURNACE FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE Printed in Canada Printed on 100 recycled paper OIL...

Страница 2: ...s and test instruments Failure to carefully read and follow all instructions in this manual can result in personal injury and or death property damage furnace malfunction WARNING Fire hazard The furna...

Страница 3: ...ions regarding any brand or type of detector CAUTION Ensure that the area around the combustion air intake terminal is free of snow ice and debris CAUTION An air pressure switch MUST be used when the...

Страница 4: ...ine or any other damaging chemicals Refer to Part 1 section 5 2 1 4 VENTING 1 4 1 General The furnaces can be vented in several ways Chimney Vented Using the Beckett AFG or Riello 40 F burner the furn...

Страница 5: ...ected to a 20 foot tall clay lined masonry chimney the thermal resistance of this type of chimney is R2 which is less than R6 The actual firing rate at 156 psig is 1 25 x 60 75 Therefore this table sh...

Страница 6: ...nal in accordance with all local and national codes The following requirements shall be considered to be minimum requirements that can be overridden by stricter local and national codes FIGURE 1 The v...

Страница 7: ...hat the band will close with an action of one strip sliding over the other not under the gear head of the draw clamp see Figure 1 8 Tighten the band clamp with considerable torque to cause the gum sea...

Страница 8: ...E BACK 5 THREAD SPIN SLEEVE BACK 10 CUT STAINLESS STEEL CORE BACK BY 3 9 FIGURE 1 3 FIGURE 1 4 FIGURE 1 1 FIGURE 1 2 FIGURE 1 5 FIGURE 1 6 INSERT STAINLESS STEEL CORE ONTO BREECH TUBE DRIVE THREE STAI...

Страница 9: ...IGURE 1 8 SEALANT FLOWING OUT FROM UNDER BAND CLAMP AT TERMINAL SEALANT OUTFLOW FIGURE 1 11 10 APPLY THE SEALANT TO THE TUBE END SEALANT OUTFLOW SEALANT FLOWING OUT FROM UNDER BAND CLAMP AT BREECH TWI...

Страница 10: ...TIGHTLY INTO RECESS INSTALL STABILIZER SHROUD CAULK TO SEAL STABILIZER SHROUD TO THE WALL FIGURE 1 13 FIGURE 1 14 FIGURE 1 12 VENT TERMINAL PRESSURE SWITCH REFER TO WIRING DIAGRAM FOR ELECTRICAL CONNE...

Страница 11: ...t 1 section 5 3 1 5 3 Outdoor Combustion Air Side wall Venting DV 2000 for a complete description 1 5 AIR FOR COMBUSTION WARNING Poisonous carbon monoxide gas hazard Comply with NFPA standards for the...

Страница 12: ...two plastics Intake pipe length DV 2000 The DV 2000 venting system has been certified for 37 equivalent m 120 equivalent feet of 3 intake pipe Count a 90 elbow as 10 equivalent feet and a 45 elbow as...

Страница 13: ...king Checking the air and turbulator settings Before starting the burner for the first time adjust the air and turbulator settings to those listed in Table 4 Once the burner becomes operational final...

Страница 14: ...e heat exchanger Wire the thermostat and condensing unit contactor as indicated in the wiring diagram Figure 6 1 9 4 Ductwork and Filter Installation Design and install the air distribution system to...

Страница 15: ...Fan Limit Control heats up to the factory set point the circulating air blower starts 7 The circulating air blower and burner motor remain on until the thermostat is satisfied Also the solenoid valve...

Страница 16: ...shut down for an extended period of time 4 Set thermostat higher than the room temperature 5 If the burner motor does not start or ignition fails turn off the disconnect switch and CALL A QUALIFIED SE...

Страница 17: ...flame should shut down before a 1 smoke reading occurs 3 Gradually block the vent outlet The burner flame should shut down before a 1 smoke reading occurs 4 If the burner does not shut down before 1...

Страница 18: ...ly from the front inspection port Also the furnace has external clean out ports so the soot does not fall into the fan compartment during the cleaning operation IMPORTANT Do not vacuum the ceramic cha...

Страница 19: ...een installed the burner will have to be removed to check the retention head 3 1 4 Nozzle Replace the nozzle with the one specified in Table 4 3 1 5 Oil filters Tank filter The tank filter should be r...

Страница 20: ...hone Day Night Dealer name and address START UP TEST RESULTS Nozzle Pressure lbpsi Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Ambient t...

Страница 21: ...3 3 4 5 AFUE From CSA B212 standard and Canadian regulation 81 5 81 0 80 3 AFUE From ASHRAE 103 standard and US regulation 81 5 81 0 80 3 RIELLO BURNER SIDE WALL INSTALLATION Burner tube insertion len...

Страница 22: ...DNS 0589 Rev C FIGURE 5 Models ODH53F100LB 3MC OCF105A12C 23 445 01 4024 05...

Страница 23: ...24 FIGURE 6 Wiring diagram ODH53F100LB 3MC OCF105A12C 445 01 4024 05...

Страница 24: ...COMPONENTS AND REPLACEMENT PARTS 25 445 01 4024 05...

Страница 25: ...PARTS LIST Model ODH53F100LB 3MC OCF105A12C B50030A 26 445 01 4024 05...

Страница 26: ...gonal nut 3 8 16NC brass F07F024 32 Washer panel peep hole B30752 33 Hexagonal flange nut 3 8 16NC brass F07O001 34A 5 breech plate B30459 34B 3 breech plate B30515 35 Gasket breech plate B30415 02 36...

Отзывы: