14
Advanced programming
Parameter Name
Default Value Range / Options Description
Programming
Devices
UHS4
UNLCDHS
For
Channel 3
(PIR Sensor)
Local Code
1
1 to 999
A number corresponding to the Local Code of all devices to be
controlled by this PIR input channel.
Sub Local Code
Not set
1 to 99
A number corresponding to the Sub Local Code of all devices to be
controlled by this PIR input channel.
Area Code(s)
Not set
1 to 999
0 to clear
A number corresponding to the Area Code of all devices to be controlled
by this PIR input channel. Up to 10 Area Codes can be set for Channel
3.
Sensitivity On
5
1 (min) to 9 (max) Sensitivity level for detecting movement when the detector is already on.
*UHS4 sets Sensitivity On and Off to the same value.
*
Sensitivity Off
5
1 (min) to 9 (max) Sensitivity level for detecting movement when the detector is off.
*UHS4
sets Sensitivity On and Off to the same value.
*
Walk Test LED
Off
On or Off
When set to On this causes a red LED to flash on the sensor when it
detects movement. Use this feature to check for adequate Sensitivity
On/Off levels.
Lux on level
(Switch level on)
400
0 (disabled) or
1 to 999
Sets a minimum light level below which the PIR sensor is enabled,
allowing lights to be turned on by movement.
Lux off level
(Switch level off)
700
0 (disabled) or
1 to 999
Sets a maximum light level above which the PIR sensor is disabled,
preventing lights from being turned on by movement.
Light Level
(maintained illuminance)
550
0 (disabled) or
1 to 999
Sets a target light level to be maintained by the lighting system.
Power Up State
On
On or Off
When power is applied to the unit the PIR sensor goes through a settling
down period of up to 40 seconds. With Power Up set to On, the outputs
go to the last levels for up to 15 seconds, then the Local On Scene
(scene 1 by default) is invoked plus the Time Adjustment Period, after
which the Local Step/Off Scene (scene 20 by default) is invoked
(assuming no movement is detected). With Power Up set to Off, the
outputs go to the last levels until movement is detected.
Disable Detector
N
Y or N
Disables detection, leaving the relay output permanently off with the
dimming output operational. This mode is used when the unit is for
maintained illuminance only.
Speed On
10
3 to 255 seconds The time between maintained illuminance messages being sent out,
after the setup period has elapsed and after occupancy is first detected.
Speed Set
3
3 to 255 seconds The time between maintained illuminance messages being sent out
during the setup period
Set Seconds
120
0 to 999 seconds
0 to disable
Determines how long the set-up period lasts on power-up or on setting
change after occupancy is first detected.