Advanced programming
Parameter Name Default Value
Range / Options Description
Programming
Devices
UHS4
UNLCDHS
When movement is detected...
Local On Scene
Fade Rate
1
1 second
1 to 20
0 to 255*
The local scene request sent to all devices with the Local Code specified
above, when movement is detected.
Area On Scene
Fade Rate
101
1 second
101 to 220
0 to 255*
The area scene request sent to all devices with the Area
Code(s) specified above, when movement is detected.
NOTE:
The Area On Scene is ignored unless one or more Area Codes are set for
the corresponding input channel and they match the Area Codes set in any output
channel.
Time adjustment
10 mins
0 (10 seconds)
1 to 99 minutes
Once the detector is turned on, this value sets how long the lights will
stay on once movement has ceased. The 10 second setting is for
commissioning only.
When no movement is detected for Time Adjustment...
Local Step Scene
Fade Rate
Timeout
20
1 second
0
1 to 20
0 to 255*
0 to 255*
If a Local and/or Area Step Scene is specified this will be requested first
when the Sensor switches off. If a Step Scene is not specified, or if it
times out, the Local and/or Area Off Scene will be implemented.
NOTE:
Area Step and Off Scenes are ignored unless one or more Area Codes are
set for the corresponding input channel and they match the Area Codes set in any
output channel.
The values of the Timeout parameters associated with Step Scenes
determine whether or not the scene is actually recalled and whether or
not to recall the Off Scene:
Local Off Scene
Fade Rate
20
1 second
1 to 20
0 to 255*
Area Step Scene
Fade Rate
Timeout
220
1 second
0
1 to 20
0 to 255*
0 to 255*
Area Off Scene
Fade Rate
220
1 second
1 to 20
0 to 255*
Time / delay table
Value
Fade rate time
Timeout delay period
0
No fade
Ignore the Step scene
1 to 59
1 to 59 seconds, in 1
second increments
1 to 59 seconds, in 1 second incre-
ments
60 to 177
1 to 59.5 minutes, in 0.5
minute increments
1 to 59.5 minutes, in 0.5 minute incre-
ments
178 to 254 1 to 20 hours, in 15
minute increments
1 to 20 hours, in 15 minute incre-
ments
255
Infinite fade
No timeout recall the specified scene
only