Ethernet I/O Modules
Example: Function 06 (0x06), Write AO
[Leading 6 bytes]
[Request]
Command:
01 02 00 00 00 06
01 06 01 08 00 3C
[Leading 6 bytes]
[Response]
Response:
01 02 00 00 00 06
01 06 01 08 00 3C
Sets the system timeout to 60 seconds
A description of the command and response is as follows:
Command:
[Leading 6 bytes]
Bytes 00-03
01 02 00 00
(Message Number)
Bytes 04-05
00 06
(Number of bytes remaining in this frame)
[Request]
Byte 00
01
(Net ID)
Byte 01
06
(Function Code)
Bytes 02-03
01 08
(AO Address)
Bytes 04-05
00 3C
(Sets the system timeout to 60 seconds)
Response:
[Leading 6 bytes]
Bytes 00-03
01 02 00 00
(Message Number)
Bytes 04-05
00 06
(Number of bytes remaining in this frame)
[Response]
Byte 00
01
(Net ID)
Byte 01
06
(Function Code)
Bytes 02-03
01 08
(AO Address)
Bytes 04-05
00 3C
(Indicates that the system timeout has been set
to 60 seconds)
ICP DAS CO., LTD.