![ICP DAS USA tET Series Скачать руководство пользователя страница 73](http://html1.mh-extra.com/html/icp-das-usa/tet-series/tet-series_user-manual_3891537073.webp)
Ethernet I/O Modules
5.
In the I/O Pair Connection section, select “
Client
” from the “
Server Mode
” drop-down options.
6.
Enter the
IP address for the PETL-7060 module
in the “
Remote Server IP
” field.
7.
Enter the
TCP Port for the PETL-7060 module
in “
Remote TCP Port
” field.
8.
Enter a
DI Count value for tET/tPET module #1
in the “
Local DI Count
” field of the “Local DI to
Remote DO section”.
For example, enter
“2”
in the
“Local DI Count”
field. This means
DI x2 of tET/tPET module #1
is
mapped to
DO x2 of the PETL-7060 module
.
9.
Enter the
DO Address
for the PETL-7060 module
in the “
Remote DO Address
” field of the “Local
DI to Remote DO” section.
For example, enter
“0”
in the
“Remote DO Address”
field. This means
DO addresses DO0 and DO1
of the PETL-7060 module
are mapped to
DI x2 of tET/tPET module #1
.
Refer to
Figure 5-11
for an illustration of how to perform the above procedure.
10.
Click the “
Submit
” button to complete the configuration.
Step 2: Configure the I/O Pair Connection on tET/tPET module #2
1.
In the eSearch Utility, select
tET/tPET module #2,
and then click the “
Web
” button to launch the
browser program and connect to the web server.
2.
Enter the password in the Login password field
(the default password is “Admin”)
, and then click
the
“Submit”
button to access the configuration page.
3.
Click the
“Pair Connection
” tab to display the Pair Connection settings page.
Refer to
Figures 5-2 to 5-3
for illustrations of how to perform the above procedure.
ICP DAS CO., LTD.
PETL/tET/tPET DIO Series User Manual, Ver. 2.1, Sep. 2014, Page: 73
ГК
Атлант
Инжиниринг
–
официальный
представитель
в
РФ
и
СНГ
+7(495)109-02-08 [email protected] www.bbrc.ru