Ethernet I/O Modules
5.
In the I/O Pair Connection section, select “
Client
” from the “
Server Mode
” drop-down options.
6.
Enter the
IP address for the PETL-7060 module
in the “
Remote Server IP
” field.
7.
Enter the
TCP Port for the PETL-7060 module
in the “
Remote TCP Port
” field.
8.
Enter a
DI Count value for the PETL-7060 module
in the “
Remote DI Count
” field of the “Remote
DI to Local DO” section.
For example, enter
“2”
in the
“Remote DI Count”
field. This means
DI x2 of the PETL-7060 module
is mapped to
DO x2 of tET/tPET module #1
.
9.
Enter the
IP Address
for the PETL-7060
in the “
Remote DI Address
” field of the “Remote DI to
Local DO” section.
For example, enter
“0”
in the
“Remote DI Address”
field. This means
DI addresses DI0 and DI1 of
the PETL-7060 module
are mapped to
DO x2 of tET/tPET module #1
.
Refer to
Figure 5-8
for an illustration of how to perform the above procedure.
10.
Click the “
Submit
” button to complete the configuration.
Step 2: Configure the I/O Pair Connection on tET/tPET module #2
1.
In the eSearch Utility, select
tET/tPET module #2
, and then click “
Web
” button to launch the
browser program and connect to the web server.
2.
Enter the password in the Login password field
(the default password is “Admin”)
, and then click
the
“Submit”
button to access the configuration page.
3.
Click the
“Pair Connection
” tab to display the Pair connection settings page.
Refer to
Figures 5-2 to 5-3
for illustrations of how to perform the above procedure.
ICP DAS CO., LTD.
PETL/tET/tPET DIO Series User Manual, Ver. 2.1, Sep. 2014, Page: 69