52
I-7011, I-7018 User Manual
Rev:B1.0
2.30 @AARE
Description
: Read Event Counter
Syntax
:
@AARE[CHK](cr)
@
delimiter character
AA
address of reading module (00 to FF)
RE
command for reading event counter
Response
:
Valid Command :
!AA(Data)[CHK](cr)
Invalid Command :
?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
!
delimiter for valid command
?
delimiter for invalid command
AA
address of response module(00 to FF)
(Data)
event counter value, from 00000 to 65535.
Example
:
Command : @01RE
Receive : !0101234
Read address 01 event counter, return 1234.
Related Command
:
Sec.2.31
@AACE
Related Topic
:
Sec.3.4
Digital Input and Event Counter
Note
: The command is for I-7011/11D/11P/11PD only