36
I-7011, I-7018 User Manual
Rev:B1.0
2.15 $AAB
Description
: Thremocouple Open Detection
Syntax
:
$AAB[CHK](cr)
$
delimiter character
AA
address of reading module (00 to FF)
B
command for reading thremocouple open status
Response
:
Valid Command :
!AAS[CHK](cr)
Invalid Command :
?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
!
delimiter for valid command
?
delimiter for invalid command
AA
address of response module(00 to FF)
S
0=close-loop detection
1=open-circuit detection, need to check the thermocouple
Example
:
Command : $01B
Receive : !010
Read address 01 thermocouple open status, return the thermo-
couple is close-loop.
Note
: The command is for I-7011/11D/11P/11PD only