41
I-7011, I-7018 User Manual
Rev:B1.0
2.20 ~AAEV
Description
: Enable/Disable Calibration
Syntax
:
~AAEV[CHK](cr)
~
delimiter character
AA
address of setting module (00 to FF)
E
command for enable/disable calibration
V
1=enable calibration, 0=disable calibration
Response
:
Valid Command :
!AA[CHK](cr)
Invalid Command :
?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
!
delimiter for valid command
?
delimiter for invalid command
AA
address of response module(00 to FF)
Example
:
Command : $010
Receive : ?01
Perform address 01 span calibration, return it is not ready for
calibration.
Command : ~01E1
Receive : !01
Set address 01 to enable calibration, return success.
Command : $010
Receive : !01
Preform address 01 span calibration, return success.
Related Command
:
Sec.2.5
$AA0,
Sec.2.6
$AA1
Related Topic
:
Sec.1.9
Calibration
Содержание Network Device I-7011
Страница 6: ...6 I 7011 I 7018 User Manual Rev B1 0 1 2 Pin Assignment...
Страница 7: ...7 I 7011 I 7018 User Manual Rev B1 0...
Страница 11: ...11 I 7011 I 7018 User Manual Rev B1 0 1 4 Block Diagram...
Страница 18: ...18 I 7011 I 7018 User Manual Rev B1 0...