ICP DAS, MDC-211-ZT user manual , v1.0 Page 30
Copyright © 2018 by ICP DAS. All rights are reserved.
Modbus Mode Settings
The fourth part is for Modbus mode settings. Modbus parameter descriptions may refer to
Section 4.2, the label name and setting descriptions please see Table 3.4 below.
#
Modbus
#
PortName PortNo. ModbusMode ModbusID Retry Timeout Interval
* ZigBee
0
1
1
3
200
30
* RS-232
1
0
1
3
150
0
* RS-485
2
1
1
3
150
20
* Ethernet
N/A
N/A
1
#
Table 3.4 Modbus protocol settings and descriptions
Item
Label Name
Note
Port Name
PortName
The name of the Modbus communication port;
the location and content are unmodifiable.
Port Number
PortNo.
The number of the Modbus communication
port; the location and content are unmodifiable.
Modbus Mode
ModbusMode
0 (Disable) / 1 (Modbus Master) / 2 (Modbus
Slave)
Ethernet fixed to Modbus Slave, no need to set
Modbus Retry
Retry
0 ~ 9
Modbus Timeout
Timeout
0 ~ 65535
Polling Interval
Interval
0 ~ 65535