IR-310-RM,
IR Controlled 10-ch High Power Relay Module
(Ver. 1.1, Jul/02/2013) 58
5.4.25 Sub-FC 75 (0x4B): Set relay pairs for interlocked mode
‧
Request
Byte
order
Description
Size
Value
00
Address
1 Byte
1 ~ 247
01
FC
1 Byte
0x64
02
Sub-FC
1 Byte
0x4B
03
Interlocked relay pairs
1 Byte
0x00 ~ 0x1F.
‧
Response
Byte
order
Description
Size
Value
00
Address
1 Byte
1 ~ 247
01
FC
1 Byte
0x64
02
Sub-FC
1 Byte
0x4B
03
Setting result
1 Byte
0x00 => OK, 0xFF=>Error.
Note:
1. For the byte of “Interlocked relay pairs”, bit 0 means the pair of relay 0 & relay 1 and
bit 4 means the pair of relay 8 & relay 9. If bit 0 is set to 1, relay 0 and relay 1 is an
interlocked relay pair.
2. The interlocked relay pairs are effective in the interlocked mode. To set the
interlocked mode, please refer to Sub-FC 67.
3. For an interlocked relay pair, e.g. RL0 and RL1, three statuses are allowed:
Interlocked Status
Relay 0
Relay 1
1
ON (NO contact)
OFF (NC contact)
2
OFF (NC contact)
ON (NO contact)
3
OFF (NC contact)
OFF (NC contact)