IR-310-RM,
IR Controlled 10-ch High Power Relay Module
(Ver. 1.1, Jul/02/2013) 51
5.4.18 Sub-FC 67 (0x43): Set the independent/interlocked mode
‧
Request
Byte order Description
Size
Value
00
Address
1 Byte
1 ~ 247
01
FC
1 Byte
0x64
02
Sub-FC
1 Byte
0x43
03
Mode
1 Byte
0=>independent, 1=>interlocked.
‧
Response
Byte order Description
Size
Value
00
Address
1 Byte
1 ~ 247
01
FC
1 Byte
0x64
02
Sub-FC
1 Byte
0x43
03
Setting result 1 Byte
0=>OK, 0xFF=>Error.
Note:
1. For the interlocked mode, please refer to Sub-FC 75 and 76 for the settings of the
relay pairs. Maximum
5
relay pairs can be set.
2. For an interlocked relay pair, e.g. RL0 and RL1, three statuses are allowed:
Interlocked Status
Relay 0
Relay 1
1
ON (NO contact)
OFF (NC contact)
2
OFF (NC contact)
ON (NO contact)
3
OFF (NC contact)
OFF (NC contact)