Installation
Section 1 Introduction
iDCS-8000 Hardware User Manual (2013/8/14, Rev: 1.43)
23
1.5.6.1
Grounding
In order to prevent the operators to get an electric shock and external noise to affect iDCS-8000 system,
the cabinet of the iDCS-8000 must set earthed. And all the metal that the operators might touch must set
earthed. The grounded system must follow “Electrical Equipment Technical Standard” Class D
specification and the earth resistance must be below 100
Ω
. (Note: There is a 3 kVDC high-tension
condenser between the S.G and F.G of iDCS-8000).
The grounded system of the iDCS-8000 must follow Class D specification. When grounding, please do not
share the ground point of the iDCS-8000 with other power system. And the distance between two ground
points must greater than 10 meters.
Содержание iDCS-8000
Страница 1: ...iDCS 8000 Remote Rugged I O System with Redundancy Hardware User s Manual...
Страница 2: ......
Страница 16: ...Section 1 Introduction Installation 16 iDCS 8000 Hardware User Manual 2013 8 14 Rev 1 43 DN AIH 04...
Страница 24: ...Section 1 Introduction Installation 24 iDCS 8000 Hardware User Manual 2013 8 14 Rev 1 43...
Страница 37: ...Digital Input Section 4 I O Module iDCS 8000 Hardware User Manual 2013 8 14 Rev 1 43 37 4 2 1 4 Pin Assignment...
Страница 43: ...Analog Input Section 4 I O Module iDCS 8000 Hardware User Manual 2013 8 14 Rev 1 43 43 4 4 1 4 Pin assignments...
Страница 46: ...Section 4 I O Module Analog Input 46 iDCS 8000 Hardware User Manual 2013 8 14 Rev 1 43 4 4 2 4 Pin assignments...
Страница 49: ...Analog Input Section 4 I O Module iDCS 8000 Hardware User Manual 2013 8 14 Rev 1 43 49 4 4 3 4 Pin assignments...
Страница 52: ...Section 4 I O Module Analog Input 52 iDCS 8000 Hardware User Manual 2013 8 14 Rev 1 43 4 4 4 4 Pin assignments...
Страница 61: ...Analog Output Section 4 I O Module iDCS 8000 Hardware User Manual 2013 8 14 Rev 1 43 61 4 5 2 4 Pin assignments...
Страница 64: ...Section 4 I O Module Pulse Input 64 iDCS 8000 Hardware User Manual 2013 8 14 Rev 1 43 4 6 1 4 Pin assignments...
Страница 90: ...Section 5 Termination Board Pulse Input 90 iDCS 8000 Hardware User Manual 2013 8 14 Rev 1 43 5 5 1 4 Wiring...