A.
About “Edit GW-7557 COM”
:
The user can set communication settings of GW-7557 com port in this
window, as shown in
Figure 59
. When user click <Save to Device> button,
these settings will be save to EEPROM of GW-7557.
Figure 59 “Edit GW-7557 COM” window
B.
About “Edit Device”
Figure 60 “Edit Device” window
Value Format
:
Support the decimal representation or the
hexadecimal representation.
Frame Type
:
The user can set the frame type for HART slave device. The
option is Short/Long.
Preamble Length
:
The user can set the preambles for HART slave device.
The range is 5~20.
Short Address
:
The user can set the address for HART slave device. The
range is 0~15. If the frame type is “Long”, the user can
omits this setting.
Manufacturer ID
:
The user can set the manufacturer ID for HART slave
device. If the frame type is “Short”, the user can omits
this setting.
Device Type
:
The user can set the device type for HART slave device. If
the frame type is “Short”, the user can omits this setting.
Device ID
:
The user can set the device ID for HART slave device. If the
frame type is “Short”, the user can omits this setting.
GW-7557 PROFIBUS/HART Gateway User Manual
(Version 1.00, Dec/2011)
PAGE: 64