4.8 P1B [CHK]<CR>
Description:
Change the CAN configuration of I-7530A module and then
reboot the I-7530A module.
¾
Syntax: P1B[CHK]<CR>
P1
Command character
B
CAN Baud rate
Table 10: CAN baud rate list
B Description
0
10K baud rate of CAN
1
20K baud rate of CAN
2
50K baud rate of CAN
3
100K baud rate of CAN
4
125K baud rate of CAN
5
250K baud rate of CAN
6
500K baud rate of CAN
7
800K baud rate of CAN
8
1000K baud rate of CAN
¾
Response:
A valid command will write the CAN configuration baud
rate into the EEPROM and then reboot the I-7530A module.
Invalid command: ?<Error Code><CR>
¾
Note:
It is necessary to enable the “Error Response” function in the I-
7530 Utility, in order to receive Syntax and/or communication error
information at the host PC.
¾
Example:
Command: P14<CR>
Set the CAN baud rate=125K into the I-7530A module and then
reboot the I-7530A module.