background image

 

 

 

 

 

 

 

4 of 4    [ I-7188EG/7188EGD ] 

http://

www.icpdas.com

 

Specifications

 of I-7188EG & I-7188EGD 

 

 

Power Supply 

 

Protection 

Power reverse polarity protection 

Input Range 

+10 ~ +30 V

DC

   

Power Consumption 

I-7188EG: 2 W , I-7188EGD: 3 W (when I/O slots are empty) 

General Environment 

 

Temperature 

Operating: -25°C ~ +75°C, Storage : -30°C ~ +80°C   

Humidity 

5% ~ 90 % RH (non-condensing) 

System

 

 

CPU 

80188, 40 MHz, or compatible 

Watchdog Timer 

Yes 

Real Time Clock 

Gives hour, minute, sec, day of week, day of month, month & year (1980 ~ 2079) 

SRAM 

512 KB 

FLASH Memory 

512 KB, Erase unit is 64 KB, 100,000 erase/write cycles 

NVRAM 

31 bytes, battery backup, data valid up to 10 years 

EEPROM 

2048 bytes, retention > 100 years.    1,000,000 erase/write cycles 

Display For I-7188EGD 

5-Digit 7-Seg. LED on the front. It can display message & value. 

Expansion I/O bus   

One optional X-board series I/O board can be plugged inside the I-7188EG/7188EGD. 

NET ID 

User-assigned by software, 1 ~ 255 

Serial Ports 

 

COM1 

RS-232: TxD, RxD, RTS, CTS, GND, Speed: 115200 bps max. Program downloads port. 

COM2 

RS-485: D+, D-, 115200 bps max. Self-tuner ASIC inside 

Ethernet 

10 Base-T, NE2000 compatible,.    Program download port 

Development Software

 

   

ISaGRAF Version 3 

IEC 61131-3 standard.    Languages: LD, ST, FBD, SFC, IL & FC 

Max. Code Size 

I-7188EG/7188EGD accepts max. 64 KB ISaGRAF code size (Appli.x8m must < 64 KB) 

PWM Output

 

 

Pulse Width Modulation Output 

All X-board series DO boards support PWM output.    8 channels max. for one controller. 
500 Hz max. for Off=1 & On=1 ms   
Output square curve:      Off: 1 ~ 32767 ms,      On: 1 ~ 32767 ms 

Counters

 

 

Parallel DI Counter

 

All X-board series DI boards support DI counter.   
8 ch. max. for one controller.    Counter value: 32 bit     
500 Hz max.    Min. ON & OFF width must > 1 ms 

Remote DI Counter 

All remote I-7000 & I-87K DI modules support counters. 100 Hz max. value: 0 ~ 65535 

Remote High Speed Counter 

Optional I-87082:100 kHz max. , 32 bit 

Protocols

 

 

Modbus Master Protocol 

Up  to 

2  COM

  Ports  (COM1,  COM2  and  COM3-in-X-board)  support  Modbus  RTU/ASCII 

Master  protocol  to  connect  to  other  Modbus  slave  I/O  devices.  Max.  Mbus_xxx  Function 
Block amount: 64. 

Modbus Slave Protocol 

Up to 

2 COM

 Ports (COM1 and one of COM2 / COM3-in-X-board) can support Modbus RTU 

Slave protocol for connecting ISaGRAF, PC/HMI/OPC Server & MMI panels. 

Modbus TCP/IP Protocol 

Ethernet  Port  supports  Modbus  TCP/IP  Slave  protocol  for connecting  ISaGRAF  &  PC/HMI. 
Max. 

4 connections

Remote I/O 

One of COM2 (or COM3:RS-485 if found) supports I-7K, I-87K I/O modules as Remote I/O. 
I-87K  series must  plug  on  RU-87P(High  profile)  or  I-87K(Low  profile)  I/O  Unit.  Max. 

64

  I/O 

modules for one PAC. 

Fbus 

Built-in COM2 Port to exchange data between ICP DAS

’s ISaGRAF PACs. 

Ebus 

To exchange data between ICP DAS

’s ISaGRAF Ethernet PACs via Ethernet port. 

SMS: Short Message Service 

One of (COM3:RS-232 or COM4:RS-232 if found) can link to a GSM modem to support SMS. 
User can request data/control the controller by cellular phone. The controller can also send 
data & alarms to user

’s cellular phone.   

Optional GSM modem: GTM-201-RS232 (GSM/GPRS modem, 850/900/1800/1900) 

User Defined Protocol 

User can write his own protocol applied at COM1, COM2 & (COM3 ~ COM8 if found) by serial 
communication function blocks. 

Modem Link 

Supports PC remotely download & monitor the controller through COM4 of X504. 

MMICON/LCD 

One of (COM3:RS-232 if found) supports ICP DAS

’s MMICON. The MMICON is featured with 

a 240 x 64 dot LCD and a 4 x 4 Keyboard. User can use it to display picture, string, integer, 
float, and input a character, string, integer and float. 

Battery Backup SRAM

 

I-7188EG/7188EGD can support up to 

1024

 retain variables with an X607/X608 plug in the 

only expansion I/O slot. 
Data can be stored in X607/X608, and then PC can load these data via COM1 or Ethernet.   
PC can also download pre-defined data to the X607/X608 
Optional:    X607: 128 KB,    X608: 512 KB 

   

Содержание I-7188EG

Страница 1: ...d COM Ports I Os or memories of I 7188EG I 7188EG supports Modbus serial protocol Modbus TCP IP protocol Modbus Master protocol Remote I O Fbus Ebus SMS Short Message Service modem link MMICON LCD and user defined protocol I 7188EGD is the same as I 7188EG but with 5 digit 7 segment LED display ISaGRAF PAC supports ISaGRAF Ver 3 Workbench 1 of 4 I 7188EG 7188EGD http www icpdas com Support IEC 611...

Страница 2: ...dbus devices Power meter temperature controller inverter Modbus RTU TCP Slave Ports Modbus RTU RS 232 485 422 max 2 COM Ports Modbus TCP IP max 4 PC HMI SCADA connection Auto report Acquisition Data Control Data I 7188EG EGD can use UDP IP to auto report acquisition data control data to local or remote internet PC Server Advantage Every I 7188EG EGD in the different location doesn t need a fixed I...

Страница 3: ...isplay RoHS 80188 40 MHz 10 Base T gray Accessories ISaGRAF 256 E ISaGRAF Workbench Software Ver 3 256 I O Tags with USB Dongle and English application book ISaGRAF 256 C ISaGRAF Workbench Software Ver 3 256 I O Tags with USB Dongle and Chinese application book ISaGRAF 32 E ISaGRAF Workbench Software Ver 3 32 I O Tags with English application book Note ISaGRAF 32 C ISaGRAF Workbench Software Ver 3...

Страница 4: ...d Counter Optional I 87082 100 kHz max 32 bit Protocols Modbus Master Protocol Up to 2 COM Ports COM1 COM2 and COM3 in X board support Modbus RTU ASCII Master protocol to connect to other Modbus slave I O devices Max Mbus_xxx Function Block amount 64 Modbus Slave Protocol Up to 2 COM Ports COM1 and one of COM2 COM3 in X board can support Modbus RTU Slave protocol for connecting ISaGRAF PC HMI OPC ...

Отзывы: