Configure the Message Configuration. here we have to select the
“
Service Type
”
of
“
Set
Attribute Single
”
. To fill in the
“
Class
”
as 4,
“
Instance
”
as 102 and
“
Attribute
”
3. For
“
Source
Element
”
select the
“
output_data
”
tag and the
“
Source Length
”
should be 4 bytes. Under
“
Communication
”
tab the
“
Path
”
should be the same as the one used to read data.
(5) This is a simple example that only will issue one read request, in a normal program some
logic have to be added to trigger the instruction again, for more information regarding this issue
refer to documentation for RSLogix5000. Now download the program to the PLC and go
“