ET-2200 Series Ethernet I/O Modules
Copyright © 2016 ICP DAS CO., Ltd. All Rights Reserved.
-
50 -
Item
Description
Default
Value
Enable PWM
This parameter is used to enable the PWM output function.
0
Enable PWM Alarm
This parameter is used to enable the PWM output alarm
function when Host/Slave watchdog timeout.
0
Duty Cycle
This parameter is used to set the duty cycle for the DO
channels. Two values are required for each DO channel.
The first value is the high pulse width, while the second is
the low pulse width. The duty cycle is in 1 ms units, and the
resolution is approximately 5 ms. (10 to 65535 ms). A value
of 0 will disable the duty cycle functions for that channel.
1000 (ms)
Update Settings
Click this button to save the revised settings to the ET-2200 module.
Note: Because of the characteristics of the relay functions, it is recommended that the PWM
on ET-2260/2261/2268 module (i.e., modules with relay functions) is not used for extended
periods of time.