INSTALLATION INSTRUCTIONS

55 SERIES ELECTRIC STRIKE

P:\INSTALLATION INST\ELECTRIC STRIKES\INST-55\INST-55.vsd     REV D     10-12    Page 1  

SDC 55 Series heavy duty electric strikes are designed 
for use with cylindrical and mortise locksets and mortise 
exit devices. Several faceplate configurations eliminate 
the need for centerline relocation, making them perfect 
for new or retrofit construction.

FEATURES:

Non-handed
No Centerline relocation
Up to 3/4” latch and 1” deadbolt

1/8”

Horizontal alignment adjustment

Field selectable Fail-Safe/Fail-Secure 
Field selectable 12/24VDC 
Stainless steel, corrosion resistant
Tamper resistant heavy duty construction
Plug-in connector
Fits ANSI 115.1 frame prep. with face modification
Patent pending

INSTALLATION

1.   Verify lock compatibility, refer to 

page 2

and 

Fig. 6, page 4.

2.   For proper frame preparation, refer to template drawings, 

Fig. 4 & 5, page 4.

2.   Factory supplied in Failsecure mode. For Failsafe mode refer 

to 

Fig. 2, page 3

3.   Determine minimum wire gauge required. See wire gauge chart below.
4. 

CAUTION!

Before connecting power wires check for proper operating

voltage at opening with a volt meter. Voltage must be /- 10% 
of strike operating voltage for proper operation.

5.   Configure strike for 12 or 24VDC operation. Refer to pigtail power 

connector wiring in 

Fig. 1, Page 3

.  Connect wires to power source.

6.   To install the strike into the frame opening:

A) Position the wiring either down or up or toward the back of the 

hollow metal frame. Make sure wires are completely clear of strike,  
so they are not pinched when mounting strike in the frame.

B) Insert mounting screws through the faceplate and secure into 

mounting tabs.

7.   After installation check horizontal alignment. There should be 1/32” 

allowable movement when the door is pulled toward the keeper. 

8.   ALIGNMENT ADJUSTMENT: Loosen mounting screws, shift strike 

body behind faceplate horizontally as shown in

Fig. 3A, page 3

then tighten mounting screws. 

9.   For excessive horizontal alignment issues, remove shim filer bar from 

the keeper as shown in 

Fig. 3B, page 3

10. The Electric Door Strike MUST be installed in such a way and in such a 

location so as not to impair the operation of an emergency exit or panic

hardware mounted on the door.

OPTIONAL MONITORING OUTPUTS:

LCM (Keeper Deadlocked Monitor)   

Signals keeper is closed and deadlocked and/or unlocked.

LBM (Latch Bolt Monitor)

Signals latch is extended into strike and/or retracted.

DBM (Deadbolt Monitor)

Signals deadbolt is extended into strike and /or retracted.

55-A  for cylindrical locksets

With 1/2" to 3/4" latch.

55-B / 55-C  For mortise 

locksets with up to a 3/4" latch

55-D / 55-E / 55-F  for mortise 

locksets with latch and deadbolt

55-ABC Universal Strike Pak for 

multiple cylindrical and mortise 

lockset applications. 

Monitoring outputs: 

Minimum 22 Gage wire recommended

OPERATION:

Fail-Secure (Power-to-Unlock):

Unlocked when energized. 

Locked when de-energized and during power failure. 

Application:

For non fire rated and fire rated doors (exception, 

may not be used on stairwell doors). May not be maintained in  
the unlocked (energized) state when used with fire rated doors.

Fail-Safe (Power-to-Lock): 

Locked when energized. Unlocked 

when de-energized and during power failure. 

Application: 

Non-fire rated doors only.

CAUTION:

Fail-safe is 

not

permitted with the UL Fire Door 

Accessory label. 

Strike Input - Minimum Wire Gauge Requirements

Voltage 

100 ft        150 ft        200 ft         250 ft         300 ft

12VDC 

18 Ga        16 Ga       14 Ga         14 Ga         ---

24VDC 

18 Ga        18 Ga        18 Ga        16 Ga        16 Ga

Warnock Hersey Tested according to:
UL 10C, 3 Hr Fire Rated (Fail-Secure only).
UL Tested according to:
UL 1034 Burglary-Resistant

801 Avenida Acaso, Camarillo, Ca. 93012  •   (805) 494-0622  •
www.sdcsecurity.com  •  E-mail: [email protected]

Содержание 55-ABC

Страница 1: ...n the door is pulled toward the keeper 8 ALIGNMENT ADJUSTMENT Loosen mounting screws shift strike body behind faceplate horizontally as shown in Fig 3A page 3 then tighten mounting screws 9 For excessive horizontal alignment issues remove shim filer bar from the keeper as shown in Fig 3B page 3 10 The Electric Door Strike MUST be installed in such a way and in such a location so as not to impair t...

Страница 2: ...nstallation No relocation of the centerline Mortise locksets with a deadbolt and a deadlatch located above the latchbolt For new and retrofit installation Deadbolt will not release All cylindrical locksets with 5 or 625 latchbolts See 55 A All mortise locksets listed with 55 B 55 C All cylindrical locksets with 5 or 625 latchbolts Adams Rite 4720 ANSI and compatible narrow stile locks Accurate Arr...

Страница 3: ... O N C LCM LMB ORG BLK WHT BLK YEL BLK ORG WHT YEL COM N O N C LCM LMB HIGH SECURITY DOOR SECURE MONITORING LCM LBM Required LCM LBM wired in series indicates door is closed latched and strike is deadlocked or door is open or unlocked FAIL SAFE MODE Door Secure or Unlocked Status FAIL SECURE MODE Door Secure or Unlocked Status FIG 1 NOTE LCM Contacts Reversed When in Failsafe Mode Monitoring Conne...

Страница 4: ... 3 3 8 015 000 375 3 8 734 4 125 4 1 8 005 1 250 1 1 4 015 000 625 5 8 625 5 8 L C 2X 5 32 MTG TAB DEPTH TYP 3 625 3 5 8 015 000 4 875 4 7 8 015 000 250 1 4 1 688 1 11 16 L C 47 64 STANDARD ANSI FIG 5 STRIKE DIMENSIONS 1 3 4 2 5 16 1 3 8 5 8 2 5 8 7 8 1 3 8 1 8 2 31 32 3 1 4 7 8 7 8 7 8 2 x 1 3 8 3 8 2 x 7 8 FIG 6 FACE PLATES All faceplates are interchangeable for application requirements 55 A 55 ...

Отзывы: