P:\INSTALLATION INST\ELECTRIC STRIKES\INST-55\INST-55.vsd     REV D    10-12    Page 3

WIRE DIAGRAM - 55 SERIES ELECTRIC STRIKE 

LCM

LBM

DBM

N/C (Powered = Open)

COM

Strike Input:

Dual Voltage
600 mA @ 12VDC
300 mA @ 24VDC

Contacts: 

SPDT, Dry, 5 Amp @ 30V

N/C (Latched = Open)

COM

N/O (Latched = Closed)

N/C (Bolt Thrown = Open)
COM

N/O (Bolt Thrown = Closed)

ORG/BLK
WHT/BLK

YEL/BLK

ORG
WHT

YEL

ORG/RED
WHT/RED

YEL/RED

STRIKE

Red
Black

+

_

12V/600mA

24V/300mA

Power

Connector

12 or 24V 

DC

Power Supply

Fail-Safe

Fail-Secure

+

-

ACCESS 

CONTROL

+ RED

~

-

+

~

~

~

YEL

YEL

- WHT

12 or 24V 

AC

Transformer

N/O (Powered = Closed)

AC to DC Rectifier

SDC BR64XL

*

*

NOTE:

Power wires must not be connected       

to supply wires larger than 18AWG

YEL/BLK

WHT/BLK
ORG/BLK

ORG
WHT

YEL

COM

N/O
N/C

LCM

LMB

ORG/BLK
WHT/BLK

YEL/BLK

ORG
WHT

YEL

COM

N/O
N/C

LCM

LMB

HIGH SECURITY DOOR SECURE MONITORING: LCM & LBM Required 

LCM & LBM wired in series indicates door is closed, latched and strike is deadlocked or door is open or unlocked 

FAIL SAFE MODE

– Door Secure or Unlocked Status

FAIL SECURE MODE 

– Door Secure or Unlocked Status

FIG. 1

NOTE:  

LCM Contacts Reversed

When in Failsafe Mode

*

Monitoring

Connectors

Cable 1

Red
White

+

_

Cable 2

SDC 12/24V Pigtail P/N CA-55-4

MOV

Remove Cover

Failsecure 
Shown

Failsafe

FIG. 3

HORIZONTAL ALIGNMENT ADJUSTMENT

3A-Nominal Alignment: 

Loosen mounting screws. 

Shift strike body behind the faceplate horizontally. 
Tighten mounting screws. 

3B-Excessive Alignment Issues: 

Remove shim filler bar from keeper.

3A

3B

FIG. 2

FIELD REVERSIBLE 
FAILSAFE / FAILSECURE

Failsecure Mode:

Factory supplied, Failsecure

Failsafe Mode:

Remove cover, push solenoid toward 

end of strike as shown below.

Содержание 55-ABC

Страница 1: ...n the door is pulled toward the keeper 8 ALIGNMENT ADJUSTMENT Loosen mounting screws shift strike body behind faceplate horizontally as shown in Fig 3A page 3 then tighten mounting screws 9 For excessive horizontal alignment issues remove shim filer bar from the keeper as shown in Fig 3B page 3 10 The Electric Door Strike MUST be installed in such a way and in such a location so as not to impair t...

Страница 2: ...nstallation No relocation of the centerline Mortise locksets with a deadbolt and a deadlatch located above the latchbolt For new and retrofit installation Deadbolt will not release All cylindrical locksets with 5 or 625 latchbolts See 55 A All mortise locksets listed with 55 B 55 C All cylindrical locksets with 5 or 625 latchbolts Adams Rite 4720 ANSI and compatible narrow stile locks Accurate Arr...

Страница 3: ... O N C LCM LMB ORG BLK WHT BLK YEL BLK ORG WHT YEL COM N O N C LCM LMB HIGH SECURITY DOOR SECURE MONITORING LCM LBM Required LCM LBM wired in series indicates door is closed latched and strike is deadlocked or door is open or unlocked FAIL SAFE MODE Door Secure or Unlocked Status FAIL SECURE MODE Door Secure or Unlocked Status FIG 1 NOTE LCM Contacts Reversed When in Failsafe Mode Monitoring Conne...

Страница 4: ... 3 3 8 015 000 375 3 8 734 4 125 4 1 8 005 1 250 1 1 4 015 000 625 5 8 625 5 8 L C 2X 5 32 MTG TAB DEPTH TYP 3 625 3 5 8 015 000 4 875 4 7 8 015 000 250 1 4 1 688 1 11 16 L C 47 64 STANDARD ANSI FIG 5 STRIKE DIMENSIONS 1 3 4 2 5 16 1 3 8 5 8 2 5 8 7 8 1 3 8 1 8 2 31 32 3 1 4 7 8 7 8 7 8 2 x 1 3 8 3 8 2 x 7 8 FIG 6 FACE PLATES All faceplates are interchangeable for application requirements 55 A 55 ...

Отзывы: