ET-2200 Series Ethernet I/O Modules
Copyright © 2016 ICP DAS CO., Ltd. All Rights Reserved.
-
52 -
Item
Description
Default
Mode
This parameter is used to define the Server mode for the
ET-2200 series module.
Mode = Disable:
Server mode (Slave).
Mode = POLL
: Poll remote DI to local DO in the Client mode
(Master).
Mode = PUSH
: Push local DI to remote DO in the Client mode
(Master).
The DI Count field must also be configured to enable Client
mode.
Disable
Remote IP
The IP address of the remote device to access.
0
Remote Port
The TCP port number of the remote device to access.
Range: 0 to 65535.
502
Net ID
The Modbus Net ID of the remote device to access.
Range: 1 to 247.
1
Scan Time
For
POLL
mode, the module will update the DI/DO states
based on the time period of the Scan Time parameter.
For
PUSH
mode, the module will update remote DO state
when the local DI state is changed. The module will also force
update remote DO when the local DI is no change during the
time period of the Scan Time parameter.
Range: 1000 to 42949672965 ms.
1000 ms
DI Count
This parameter specifies how many digital I/O channels are
mapped.
Range: 1 to 16; 0= Disable.
0
DI Addr
For
POLL
mode, this parameter specifies the base address of
the
Remote DI device
that will be mapped to the
Local DO
register
. The range depends on the type of remote device being
used.
For
PUSH
mode, this parameter specifies the base address of
the
Local DI register
that will be mapped to the
Remote DO
device
. The range depends on the type of ET-2200 module being
used.
0