6
Version 1.0.1
DNP-211 User Manual
2022/06/01
VGA
1 (reserved)
Ethernet
RJ-45 x 2, 10/100/1000 Based-TX (Auto-negotiating,
Auto MDI/MDI-X, LED indicators)
USB 2.0
2 (reserved)
Console Port
RS-232 (RxD, TxD and GND); Non-isolated
ttyO2
RS-485 (Data+, Data-); Non-isolated
ttyO4
RS-232 (RxD, TxD and GND); Non-isolated
ttyO5
RS-485 (Data+, Data-); 2500 VDC isolated
Protocol
Modbus
Identity
Modbus TCP server
Function
1, 2, 3, 4, 15, 16
Connection Max. 16 Modbus TCP clients
DNP3
Identity
DNP3 master
Connection Max. 5 MMS clients
Group
1, 10, 12, 20, 30, 40, 41
Data Point
DI: 8192
DO: 8192
Count: 2048
AI: 2048
AO: 2048
Power
Supply Voltage
+12 to +48 VDC
Consumption
4.8 W
Connector
3-pin Removable Terminal Block
Mechanism
Dimensions
35 mm x 167 mm x 119 mm
Casing
Metal
Installation
DIN-Rail
Environment
Operating Temp.
-25°C ~ +75°C
Storage Temp
-30°C ~ +85°C
Humidity
10 ~ 90% RH, non-condensing