A-3. CL-203-E DCON Command Sets
- 98 -
Command
Description
@AABA
Read beep on alarm time
response
!AAHH, HH in hex, 0: disabled, 1 ~ 250: beep on alarm
time in seconds, 251: beep on alarm continuously
@AABAHH
Set beep on alarm time
HH in hex, 0: disabled, 1 ~ 250: beep on alarm time in seconds,
251: beep on alarm continuously
@AABE
Read enable/disable beep on alarm
response
!AAHH, HH in hex, bit 0 for channel 0, bit 1 for channel 1,
etc, for each bit, 0: disabled, 1: enabled
@AABEHH
Enable/disable beep on alarm
HH in hex, , bit 0 for channel 0, bit 1 for channel 1, etc, for each bit,
0: disabled, 1: enabled
@AACH
Clear all high latched analog inputs to the current values
@AACHN
Clear channel high latched analog input to the current value, N = 0
for CO, 1 for CO2, 2 for relative humidity, 3 for temperature in
0.01°C, 4 for temperature in 0.01°F, 5 for dew point temperature in
0.01°C, 6 for dew point temperature in 0.01°F
@AACHCN
Clear high latched alarm of a channel, N = 0 for CO, 1 for CO2, 2 for
relative humidity, 3 for temperature in 0.01°C, 4 for temperature in
0.01°F, 5 for dew point temperature in 0.01°C, 6 for dew point
temperature in 0.01°F
@AACL
Clear all low latched analog inputs to the current values
@AACLN
Clear channel low latched analog input to the current value, N = 0
for CO, 1 for CO2, 2 for relative humidity, 3 for temperature in
0.01°C, 4 for temperature in 0.01°F, 5 for dew point temperature in
0.01°C, 6 for dew point temperature in 0.01°F
@AACLCN
Clear low latched alarm of a channel, N = 2 for relative humidity, 3
for temperature in 0.01°C, 4 for temperature in 0.01°F, 5 for dew
point temperature in 0.01°C, 6 for dew point temperature in 0.01°F
@AADACN
Disable AI alarm of a channel, N = 0 for CO, 1 for CO2, 2 for relative
humidity, 3 for temperature in 0.01°C, 4 for temperature in 0.01°F, 5
for dew point temperature in 0.01°C, 6 for dew point temperature in
0.01°F