CL-200 Series User Manual Version 1.2.0 Apr. 2019
- 61 -
DO tab
On this DO tab, users can control the relay to output ON or OFF status, and set the
power on value and safe value for the relay output.
When any one of the high/low limit alarm for CO/CO
2
concentration, temperature,
humidity and dew point is enabled, the functions on this tab are all disabled as
below.
If all the alarm events are disabled, the functions are available as below:
When the buttons are
clicked, the DO status
will be set as the
Power On value or
Safe value.
Select one of the radio button and the
checkbox next to DO will display the
setting for selected item.
The checkbox can be used to control and display the DO status.
Check/Uncheck the checkbox can control the relay output.
Checked/Unchecked symbol also means the DO status