C-12. CL-213 / CL-213-E Modbus Address Mappings (Base 1)
- 215 -
Address Description
Attribute
30513 ~
30520
40513 ~
40520
High latched analog input value of channel 0 to 7
channel 0: CO in 1ppm,
channel 1: CO
2
in 1ppm,
channel 2: PM2.5 in 1ug/m
3
,
channel 3: relative humidity in 0.01%,
channel 4: temperature in 0.01°C,
channel 5: temperature in 0.01°F,
channel 6: dew point temperature in 0.01°C,
channel 7: dew point temperature in 0.01°F
R
30545 ~
30552
40545 ~
40552
Low latched analog input value of channel 0 to 7
channel 0: CO in 1ppm,
channel 1: CO
2
in 1ppm,
channel 2: PM2.5 in 1ug/m
3
,
channel 3: relative humidity in 0.01%,
channel 4: temperature in 0.01°C,
channel 5: temperature in 0.01°F,
channel 6: dew point temperature in 0.01°C,
channel 7: dew point temperature in 0.01°F
R
30556
40556
Module reset status, 1: power-on, 2: watchdog, 3: software reset
command
Only for Modbus TCP protocol
R
40558
Ethernet host watchdog timeout value, 5 to 65535, in second, 0 to
disable.
Only for Modbus TCP protocol
R/W
30559
40559
Ethernet host watchdog timeout count.
Only for Modbus TCP protocol
R
30560
40560
Module name, 0x0213
Only for Modbus TCP protocol
R
40564
TCP disconnection timeout value, 5 to 65535, in second, 0 to
disable.
Only for Modbus TCP protocol
R/W
40565
Module reset timeout value, 30 to 65535, in second, 0 to disable.
Only for Modbus TCP protocol
R/W
40865
RTC year, 2000 to 2159
R/W
40866
RTC month, 1 to 12
R/W
40867
RTC date, 1 to 31
R/W
40868
RTC hour, 0 to 23
R/W