CAN-2024C user’s manual (Revision 1.10, Mar/02/2016) ------
13
3h
Error Mode AO channel 2
UNSIGNED 8
RW
0
4h
Error Mode AO channel 3
UNSIGNED 8
RW
0
6444h
0h
Number of Analogue Outputs
UNSIGNED 8
RO
4
1h
AO error value of channel 0
UNSIGNED 32
RW
0
2h
AO error value of channel 1
UNSIGNED 32
RW
0
3h
AO error value of channel 2
UNSIGNED 32
RW
0
4h
AO error value of channel 3
UNSIGNED 32
RW
0
2004h
0h
Number of Analogue Outputs
UNSIGNED 8
RO
4
1h
Type Code of AO Channel 0
UNSIGNED 8
RW
0x33
2h
Type Code of AO Channel 1
UNSIGNED 8
RW
0x33
3h
Type Code of AO Channel 2
UNSIGNED 8
RW
0x33
4h
Type Code of AO Channel 3
UNSIGNED 8
RW
0x33
Table 3-8
This object 0x2004 controls the output type of the CAN-2024C. There are six
kinds of output ranges for choices. These ranges and corresponding values
are listed below.
.
Type Code Value
Output Type
Output Range
Hexadecimal
0x30
Current
0 ~ 20 mA
0x0000 ~ 0x7FFF
0x31
Current
4 ~ 20 mA
0x0000 ~ 0x7FFF
0x32
Voltage
0 ~ 10 V
DC
0x0000 ~ 0x7FFF
0x33 (default)
Voltage
-10 ~ +10 V
DC
0x8000 ~ 0x7FFF
0x34
Voltage
0 ~ 5 V
DC
0x0000 ~ 0x7FFF
0x35
Voltage
-5 ~ +5 V
DC
0x8000 ~ 0x7FFF