2.3.2 JP1, JP2 : D/A Int/Ext Ref Voltage Selection
If JP1/2 select
internal reference
, then JP3 select
5V/ 10V
internal reference voltage.
If JP1/2 select
external reference
, then
ExtRef1, CN2 pin 17
, is the external reference
voltage for DA channel 1. and
ExtRef2, CN2 pin 19
, is the external reference voltage for
DA Channel 2. If user provides AC +/- 10V external reference voltage, the D/A output
voltage may be AC -/+ 10V
2.3.3
JP8 : A/D Trigger Source Selection
Ch 1 = INT
Ch 2 = INT
(default)
JP1/2(vref)
Ch 1 =EXT
(ExtRef1)
Ch 2 =EXT
(ExtRef2)
Ch 1 = INT
Ch 2 =EXT
(ExtRef2)
JP1/2(vref)
Ch 1 =EXT
(ExtRef1)
Ch 2 = INT
JP1/2(vref)
JP1/2(vref)
EXTTRG
INTTRG
Internal
Trigger
(default)
EXTTRG
INTTRG
External
Trigger
The A-812PG supports two trigger type,
internal trigger
and
external
trigger.
The external trigger comes from
ExtTrg, CN3 pin 1
. There are two
types of internal trigger,
software trigger
and
pacer trigge
r.
A-812PG Hardware Manual (Ver.1.2, Sep/2005, IPH-004-12) -----