1

24 VDC

Power supply : 18...30 VDC

5-Pin Plug with RS 485 – Communication and Digital Output Q1:

3

GND

4

Communication

Ground : 0 V

RS 485 A

5

Analog output QA

RS 485 B

2

Pulse / Frequency output

Alternative:

Digital Output Q1
Freely adjustable ranging from 0.1 to 3000 ml/pulse in 0.1 ml/pulse steps,
npn-Transistor, max. load 30V/100mA.
Max. Voltage must be less than the supply voltage.

1. Empty pipe output

2. Dosing output

3. Upper or Lower Limit output

4. Negative flow

Configurable output of 0V or 24V when pipe is empty.

Configurable output of 0V or 24V

Configurable output of 0V or 24V when reaching upper or lower limit

Configurable output of 0V or 24V when liquid flows in negative direction

www.iconprocon.com | [email protected] | 905.469.9283

09

Ultrasonic Flow Meter

UltraFlo

®

 2000 SERIES

Fig. 8: Pin code: Connection plug / socket for 8-pin version

1

24 VDC

2

Power supply : 18...30 VDC

8-Pin Plug with 1-Wire Communication

Pin

Function

Description

3

GND

4

Digital output Q2 Functions:

Ground : 0 V

Digital output Q2
Configurable npn- or pnp-transistor, max. load 100mA*.
Max. voltage must be less than the supply voltage

1. Empty pipe output

2. Dosing output

3. Pulse / Frequency output

4. Upper or Lower Limit output

5. Negative flow

Configurable output of 0V or 24V when pipe is empty.

Configurable output of 0V or 24V

Freely adjustable ranging from 0.1 to 3000 ml/pulse in 0.1 ml/pulse steps.

Configurable output of 0V or 24V when flow reaches upper or lower limit.

Configurable output of 0V or 24V when liquid flows in negative direction.

6

5

1

4

8

7

3

2

6

5

1

4

8

7

3

2

Digital Output Functions

Digital Output Q1
Configurable npn-or pnp transistor, max. load 100mA*.
Max. voltage must be less than the supply voltage

1. Pulse / Frequency output

2. Empty pipe output 

3. Dosing output

4. Upper or Lower Limit output

5. Negative flow

Freely adjustable ranging from 0.1 to 3000 ml/pulse in 0.1ml/pulse steps,

Configurable output of 0V or 24V when pipe is empty.

Configurable output of 0V or 24V

Configurable output of 0V or 24V when reaching upper or lower limit

Configurable output of 0V or 24V when liquid flows in negative direction.

Содержание truflo UltraFlo 2000 Series

Страница 1: ...ltrasonic Flow Meter UltraFlo 2000 SERIES Operating Manual www iconprocon com sales iconprocon com 905 469 9283 Ultrasonic Flow Meter UltraFlo 2000 SERIES 400 0 5496 Flow Total GAL 0 50 100 GPM Set Es...

Страница 2: ...Menu Organization for 5 Pin Version Menu Organization for 8 Pin Version Functionalities of Flow Meter Default Settings Exchange of Measuring Device Behavior of the Temperature Sensor Possible Error T...

Страница 3: ...ns in this operating manual Intended Use Assembly electrical installation commissioning and maintenance of the flow meter must be carried out by qualified trained personnel The qualified personnel mus...

Страница 4: ...digital output or displayed on the display menu The protection class is IP 67 Flowmeter meets the general EMC immunity requirements according to CE EN 61000 6 3 EN 61000 4 2 EN 61000 4 3 EN 61000 4 4...

Страница 5: ...mm s Reference conditions VDE VDI 2642 Repeatability 0 5 Data Interface Data Interface for Parameterize Electrical Power Input 24VDC 3 6W Power Supply 18 30VDC Connection plug 5 pins plug 8 pins 10 w...

Страница 6: ...00 to avoid cavitation Insure all mechanical connections are tight Particles present in the flow stream may result in measuring errors Note The housing of UltraFlo is labeled with an arrow symbolizing...

Страница 7: ...s achieved if bubbles do not pass through UltraFlo 2000 Series IMPORTANT The UltraFlo 2000 must be installed without mechanical tensions on the existing pipe system The flowmeter may be damaged if the...

Страница 8: ...min 20mA depending on diameter Empty pipe Alert 3 5mA 4 1 3 5 2 4 3 1 5 2 2 Pulse Frequency output Alternative Digital Output Q1 Freely adjustable ranging from 0 1 to 3000 ml pulse in 0 1 ml pulse st...

Страница 9: ...ital output Q2 Functions Ground 0 V Digital output Q2 Configurable npn or pnp transistor max load 100mA Max voltage must be less than the supply voltage 1 Empty pipe output 2 Dosing output 3 Pulse Fre...

Страница 10: ...24V Reset of the counter by a rising edge of 24V Creeping suppression is deactivated as long as there are 24V at the input 8 Shielding EMC safety 1 24 VDC 2 Power supply 18 30 VDC 8 Pin Plug with RS...

Страница 11: ...according to section 3 2 Dosing 1 Flowmeter as a dosing device Adjusting the manufacturer pre set parameters requires Programmtool Digital output Q1 function and behavior Analog output QA function and...

Страница 12: ...pears in the display This need not be the adjusted enabled parameter The enabled parameter appears inverted and possibly visible by scrolling NOTE Functions marked with asterisk are only available for...

Страница 13: ...s Pulse Output Off Dosing Negative Flow Upper Limit Lower Limit Empty Pipe NPN normal open NPN normal closed PNP normal open PNP normal closed Flow Temperature Off 0 20mA 4 20mA max Range min Range Ou...

Страница 14: ...tart Stop Version Values Configuration Status Off Dosing Reset Counter Creeping Flow Off Set Offser Pulse Value Upper Limit Lower Limit Function Logic ml s l l min m3 Gal h Gal l min l Off Strong Medi...

Страница 15: ...nit of the flow value The letters after the correspond to the unit of the volume value Example ml s l Here the flow appears in the unit ml s milliliters per second and the daily amount in l liters Gal...

Страница 16: ...92 l min in steps of 0 006 l min Filter options for Analog Output Filter off soft medium strong 100 16ms 0 3s 1s 4 2s 100 80 60 40 20 0 Response time Analog Output Off Soft Medium Strong Value Time s...

Страница 17: ...of 25 1 Creeping Suppression switch on 2 Creeping Suppression switch off 1 2 1 05 0 9 0 75 0 6 0 45 0 3 0 15 0 25 Flow l min Pulse Analog output Active Inactive Active Inactive Active 1 2 2 1 Creeping...

Страница 18: ...esistance 24V Normal Open 24V 0V Above Upper Limit 0V High resistance 24V High resistance Upper Limit Output Below Lower Limit Between the Limits 0V Normal Closed 0V High Resistance 0V Normal Open Hig...

Страница 19: ...9 9283 19 Ultrasonic Flow Meter UltraFlo 2000 SERIES 20 mA the upper limit of the relevant measurement 4 mA the lower limit of the relevant measurement 3 5 mA empty pipe The values here signify for 4...

Страница 20: ...r Filter off soft medium strong 100 16ms 0 3s 1s 4 2s 100 80 60 40 20 0 Response time Analog Output Off Soft Medium Strong Value Time s 0 1 2 3 4 24 22 20 18 16 14 12 10 8 6 4 2 0 0 10 20 10 20 30 Cur...

Страница 21: ...Temperature Default Setting Flow Here the value is set at the 0 or 4 mA to be output Min Range Setting Range 0 900 00 l min in 0 06 l min steps Default Setting 0 l min Here the value is set at the 20...

Страница 22: ...ess After changing configurations via Programmtool a restart of the device is necessary to activate the doing input function Flowmeter has a digital input that is programmable to following functions d...

Страница 23: ...should be saved and copied on the new flowmeter b when using the dosing function set a quantity If the device requires a configuration change the display and programming unit Programmtool is required...

Страница 24: ...portant that you provide a technical contact person including phone and fax number as well as e mail address The integrated temperature sensor has no direct contact to the liquid and is used to calcul...

Страница 25: ...When power supply is less than 18V the outputs are inactive When over load of the digital outputs is detected 100mA outputs are inactive When the flow is less than an adjustable limit and the output i...

Страница 26: ...o electrical mechanical or chemical damage due to improper accidental or negligent use 3 have been modified or altered 4 anyone other than service personnel authorized by Icon Process Controls Ltd hav...

Страница 27: ......

Отзывы: