The configuration mode is used to set the SC3006 to match your heating/cooling system. The SC3006 functions
with heat pump, air conditioning, gas, oil or electric heat systems.
1. To enter the configuration mode, simultaneously hold down the and buttons while the SC3006 is in OFF mode.
2. Press the or button to change settings within each screen.
3. Press the button to advance to the next screen.
Note:
The button will return you to the previous screen.
4. To exit configuration mode, hold the button for 6 seconds.
Configuration Mode Settings
The setup screens for configuration mode are as follows:
1.
Temperature scale (F or C) – Choose Fahrenheit or Celsius.
Press the or button to select.
Press the button to advance to the next screen.
2. Differential (1°F - 5°F) (1°C - 3°C) – Set the number of degrees between your “turn on”
temperature and your “setpoint” temperature.
Press the or button to set differential value.
Press the button to advance to the next screen.
3. Deadband (1°F - 9°F) (1°C - 5°C) – Set the minimum number of degrees between your heating
system activation and your cooling system activation.
Press the or button to set deadband value.
Press the button to advance to the next screen.
Configuration Mode