0
The configuration mode is used to set the SC2010 to match your heating/cooling system. The SC2010 functions with heat
pump, air conditioning, gas, oil or electric heat systems.
To configure the SC2010, perform the following steps:
1. Remove the cover of the thermostat by gently pulling on one of the corners.
2. Simultaneously hold the
SW5
and
SW6
buttons in for 5 seconds while the SC2010 is in
OFF
mode.
3. Press the or button to change settings within each screen.
4. Press the
SW6
button to advance to the next screen.
Note:
The
SW5
button will return you to the previous screen.
5. To exit configuration mode, slide the
Mode
switch to
Heat
or
Cool
.
Configuration Mode Settings
The nine (9) setup screens for Configuration Mode are as follows:
1.
Heat pump
and
Non Heat Pump –
Press the or button to configure as heat
pump, or non-heat pump system. For heat pumps, there will be an anti-short
cycle delay for heating and cooling
• 1 = Heat pump system
• 0 = Non-heat pump system
Press the
SW6
button to advance to the next screen.
2.
Temperature Scale (F or C) –
Choose Fahrenheit or Celsius.
Press the or button to select.
Press the
SW6
button to advance to the next screen.
Configuration Mode
3.
Temperature Differential (1°F to 3°F) (0.5°C to 1.5°C) –
Set the number of degrees
between your “setpoint” temperature and your “turn on” temperature.
Press the or button to set differential value.
Press the
SW6
button to advance to the next screen.
DIFF
SET
SET
SET