Residual Risk Management
36
CORROSION
–
Carry out water analysis at the necessary time intervals (refer to user's manual).
–
Perform water treatments in order to bring the characteristic values back within the limits specified in the use and mainte-
nance manual.
–
Keep water at a temperature above 60 °C to facilitate deoxygenation.
PRESENCE OF SLUDGE
–
Carry out water analysis at the necessary time intervals (refer to user's manual).
–
Perform water treatments in order to bring the characteristic values back within the limits specified in the use and mainte-
nance manual.
–
Blowdown by working on the drain valves present on boiler bottom.
EXTERNAL LOADS
–
Boiler fittings shall not be considered as pipe supporting points (refer to the user's manual).
–
It is good practice to allow for expansion joints and suitable supports for the pipes connecting the boiler to the system (refer
to the user's manual).
–
Generators are sized only for the loads resulting from pressure, temperature and type of contained fluid (refer to the user’s
manual).
POWER SUPPLY
–
A mains voltage control device has been inserted inside the electric system (voltage asymmetry-phase presence-phase
sequence).
–
Make sure that the panel power supply complies with the indications given in the attached wiring diagram.
ELECTRIC PANEL ACCIDENTAL OPENING
–
Door lock connected to main switch.
–
Voltage adhesive label.
–
Inner parts can be accessed using a special key available only to professionally qualified staff.
STRAY CURRENTS
–
Make sure that no stray currents are present on the generator
–
Make sure the generator is properly earthed.
–
Check the plant’s electrical system.
DOOR ACCIDENTAL OPENING
–
Before opening the door, check that the burner is off and disconnected.
PUMP SHUT-OFF VALVE CLOSING
–
Switch off the burner and the pump before closing the shut-off valve.
–
Water minimum level has to be continuously monitored through the level indicator.
WATER SUCTION FILTER
–
Pump suction filter must be cleaned at regular intervals.
–
Water minimum level has to be continuously monitored through the level indicator.