AUTOMATIC LEVEL REGULATOR
It is of the electric conductivity type, with electronic relays in the electric panel. Operation involves water pump start and stop and
a low level safety device:
Probes in the cylinder:
6 Pump stop
7 Pump start-up
8 Burner shut off 1st safety device and alarm triggering
9 Burner shut off 2nd safety device and alarm triggering
NOTE: It is recommended to add to the alarm buzzer in the boiler room
also an acoustic or visual warning in a usually manned place.
SAFETY LEVEL SWITCH
The safety level switch includes several parts (2 level rods, 2 probes, cylinder inside or outside the generator, electric cables, 2
electronic relays with conductivity trip point, electrical operation logic) suitable for preventing water level in boilers from getting
too low as this could result in overheating of the parts in contact with combustion products.
The principle for measuring and controlling the level is based on water electric conductivity. To ensure level switch proper
operation, the following conditions must be met:
• Water conductivity
• Boiler temperature
• Pressure
>250 uS/cm
<210°C
<20 bar
(See par. "Operating water").