Adjustment and control system
40
ACCESS PATH
:
→
BLOWDOWN VALVE
No.
Description
Range
unit of
measurement
Default
Reading
Writing
Visibility
06.01
Opening time of the blowdown valve.
Duration of the programmed opening of the blowdown valve.
When the value is 0, the valve does not open. The valve symbol
flashes on the display.
0 - 99
s
10
USER
USER
If the
blowdown
valve is
enabled
06.02
Pause time of the blowdown valve.
Time between one opening and the following one of the
blowdown valve.
1 - 999
min
60
USER
USER
If the
blowdown
valve is
enabled
SERVICE PARAMETER MENU
ACCESS PATH
:
→
FORCING
No.
Description
Reading
Level
Writing Level
Visibility Conditions
10.01 Burner enabling
OEM
OEM
Always
10.07 Blowdown valve
OEM
OEM
Only if enabled
10.08 Pump 1 Modulation
SERVICE
SERVICE
Only if the level transducer is enabled
10.09 Pump 2 Modulation
SERVICE
SERVICE
Only if the second pump and the level
transducer are enabled
10.11 Pump 1 Enabling
OEM
OEM
Always
10.12 Pump 2 Enabling
OEM
OEM
Only if the second pump is enabled
10.13
TDS
Valve Enabling
OEM
OEM
Only if enabled
10.14 Acoustic alarm
SERVICE
SERVICE
Always
10.15 Alarm for operation without continuous supervision expired
SERVICE
SERVICE
Always
10.06 Cumulative alarm signal
SERVICE
SERVICE
Always
10.16 Energy saver pump
OEM
OEM
If enabled
10.17 Feed valve modulation (OC1)
SERVICE
SERVICE
Only if expansion 2 and relevant function are
enabled
10.18 Steam valve modulation (OC2)
SERVICE
SERVICE
Only if expansion 2 and relevant function are
enabled
10.20 Dosing pump (V1A outlet)
OEM
OEM
Only if expansion 2 and relevant function are
enabled
10.26 Enabling duration
SERVICE
SERVICE
Always
10.27 Enable forcing
SERVICE
SERVICE
Always
Notes
–
By accessing the forcing parameter, all the available outlets will be displayed. The desired status of each outlet can be set.
–
Forcing is interrupted by quitting the menu, unless an additional duration is entered whose countdown starts upon quitting
the menu.
–
Outlets can be forced also for an unlimited time (HOLD).
–
Whenever accessing the forcing menu, the default parameters will be available, except for the unlimited time forcing. Forcing
will be disabled upon PLC rebooting and after any level change.
Содержание 86440350
Страница 78: ...Appendixes for Technical Personnel 78 ...
Страница 79: ...Appendixes for Technical Personnel 79 ...