Installation guide
NP800R
Date : 01/2012
Print :23/08/2012
Sheet :
8
Issue : a
Mounting and fixing - Flush rear connection
3.1.2
NP800R with Flush rear connection case
is dedicated to the revamping
of CEE relays series 7000 and 700
with Flush Rear connection case.
The set-up of relay series 7000 and 700 may be different from one equivalent NP800R, (Ex IMM 7990 relay
size R3 with a NPM800R in size R2) to hide the empty space a blank cover R1 is available. (Kit
« NP800RCACHE.R1 »
The protective relays NP800R are multifunctional and can replace many analogue relays. In order to hide the
location of old relays, shutters in size R1, R2 and R3 are available; « KIT/OBTU.R1 » ; « KIT/OBTU.R2 » ;
« KIT/OBTU.R3 ».
The package includes the base kit (a new base, 4 mounting - screws), additional connectors and the
protective relay NP800R.
For details of size and mounting see the diagram 40037
Operation of replacement and connection - Flush rear connection
3.1.3
3.1.3.1 Removal of relay 7000 or 700 - Flush rear connection
Put out of service the electrical system in compliance with safety
Unscrew the four fixing rods and pull out the 7000 or 700 relay
Identify and disconnect the wires of the terminals
Remove the mounting - cradle and the base
Mounting
cradle(x 4)
Fixing rod (x 4)
Base