background image

1.  Installations will run most efficiently with 3/8” pipe runs with the Ice Solar standard 

system configurations.  Ensure the whole 20m length of 3/8” (9mm) copper coil is 

used.  NOTE: flare connectors require flaring tool that has a 3/8” (9mm) setting.  

Only use 1/2” pipe if running more than 3 collectors in series.  Or for commercial 

installations size is according to system specific configuration.

2.  Run the hot return line fist.  Select the shortest pipe run for highest collection effi-

ciency.  ie closest side of solar collector’s manifold to the cylinder.  Use the balance 

of the coil for the return line.  This helps with the self cooling (CMAX) setting for 

when cylinder reaches temperature.

3.  Use only high temperature jointing methods. In stagnation the solar collector can reach 

temperatures of up to 200 degrees C.  ie. braise welding for roof fittings is failsafe (not 

on air vent), Gasoila/Teflon or Heldite/Teflon are both acceptable for these products 

are rated to over 200 degrees C. Hemp and graphite is not recommended. Use high 

temperature washers for fixing swivel unions onto manifold.

4.  Connect air vent AAV (vertical position) and probe assembly onto the hot water 

return side of the manifold.  The air vent captures air before it returns to the cylinder 

and the probe reads temperature as it leaves the manifold.  The probe socket is IP68 

rated for a secure weather and bird resistant socket for the PT1000 (T1) sensor.

5.  Choose the penetration entry points for copper pipe through roof.  Take into consid-

eration exposure from ground view (ie. hide behind manifold to reduce visibility for a 

tidy job).  Ensure no roof support members will interfere with penetration points, and 

there is enough room to achieve nice connection onto manifold fixing points.  Then 

drill a 25mm-32mm hole through highest point of roof profile for the 3/8” (9mm) pipe 

through roof flashing.  Drill a second 10mm-12mm hole through highest part of roof 

profile for the PT1000 (T1) cable that will line up with the cable penetration lug in the 

flashing, there are two to choose from, so choose which ever is easiest for cable run.  

PLUMBING

IMPORTANT ensure PT1000 (T1) cable can not come in contact with the high tem-

perature return pipe and that it can not get damaged by sharp edges of roof material. 

Carefully cut high temperature flashing at the level above the first rib, this is the 3/8” 

mark.  Choose one of the separate cable nibs of the flashing and cut top of this nib to 

run the PT1000 (T1) cable. Run the insulation up to the flashing DO NOT run insula-

tion through flashing.

6.  Complete plumbing as shown on schematic of front cover of this manual.  Turn water 

on and check system for leaks.

•  Connect and close ball valves, non-return and pump on cold side to draw cold 

water up to solar panel.  Install ball valve before pump and after non-return valve 

so that these items can be easily serviced in the future without draining the water 

from the manifold.

•  It is good practice to create thermal breaks if possible by bringing the hot water 

return pipe below the level that it enters into the cylinder by approximately 

200mm, then back up into the cylinder.  This prevents heat loss by heat drifting 

up the line.  This is particularly important for solar/wetback installations and low 

pressure installations.

•  The circulation pump must be installed to draw the cooler water from the lower 

section of the cylinder and circulate this water through the collector before 

returning back to the cylinder at a point higher than the draw-off (150mm-200mm) 

using dedicated solar ports or a 4-Way valve.

•  Circulation pump MUST be mounted so that the cylindrical shape of the pump is 

in a horizontal position to avoid accumulation of air that will burn the pump out.

•  Check all connections are complete then fill cylinder.
•  Open ball valves and check whole system for leaks.
•  Ensure automatic air vent on roof is open to allow air to escape.
•  Bleed (purge) pump of air, using the bleed screw on pump.
•  Setting Pump Speed – set pump speed according to the hot water systems pressure 

Mains Pressure = Pump Speed 1: Medium Pressure = Speed 2 : Low Pressure = Speed 3

•  Cover air vent with jacket.
•  Insulate copper pipe above roof line.  It is not necessary to cover brass fittings 

unless system is in a corrosive environment.  Covering fittings can create difficul-

ties in future maintenance of system.

7.  Smear heat past around the top copper head of each heat-pipe.  The heat-paste is 

required for high efficiency heat transfer; it also acts as a lubricant on installation to 

allow the Heatpipe to slide into the copper socket inside the manifold.  Hold thumb 

over tube-collar to keep these components together against top of borosilicate 

glass tube, then slide the inner copper heat-pipe out by approximately 6-8 inches 

(150mm-200mm).  Gently resting bottom end of glass tube on foot rail, and holding 

onto inner copper pipe, look up into manifold, and slide tip of Heatpipe all the way up 

into copper manifold socket.  Giving the copper pipe a little wriggle as it goes in will 

ensure you feel it slide all the way up into this socket.  Then move the glass up with 

the tube-collar to the manifold, and screw on the tube-collar.  Still holding the glass so 

it can not slide down, slide on the tube cup base and ensure it locks securely into place

Install to ASNZS3500.4 G12, G12AS2, NZS3501
When installing or repositioning cylinders ensure that parts have access for ease 

of future maintenance and operation, in particular elements, anodes, valves and 

pumps.  Ensure pumps are positioned with accessible air bleed and speed dial.
WARNING: Systems must be installed so that there is a minimum of 2 meters head 

of pressure that is continuously maintained above the location of the manifold (top 

of solar collector).  Failing to provide sufficient pressure can result in shortened life 

expectancy of pump and will void warranty.
WARNING: Only use high temperature rated valves.  Pipework for cylinder cold 

feeds should be done in copper from the valve kit to the cylinder, as backwater ex-

pansion can be, at times, of high temperature that plastic plumbing systems are not 

suitable for.
CAUTION: Once the heat-pipes are installed DO NOT close both hot and cold ball 

valves to solar collector without draining the manifold, as heat expansion may create 

leaks.  One of these valves should always remain opened during maintenance to 

allow water to expand back into the cylinder.

Содержание STD20

Страница 1: ...lar energy equipment If you have any questions please contact us Commissioning with Customer Please ask customer to be available at the end of the day estimated completion time for commissioning and to go through user operation INSTALLATION INSTRUCTION MANUAL June 2020 ...

Страница 2: ...RAISED UP STANDS TILE ROOF CORRUGATED ROOF METAL TILE ROOF ...

Страница 3: ...L 1545 37 L 1469 42 L 1381 46 L 1278 Adjustable angle range between 26 46 Degrees Sections 4 and 5 should be set to suitable height adjust these first and bolt together Sections 3 and 6 should be accurately adjusted and cut to suit the panels height Bolt holes may need to be re drilled to be able to assemble at desired height 1 Outrigger 35mm wide x 30mm height x 3mm powdercoated Aluminium U chann...

Страница 4: ...turer s roof fixing requirements 6 Drill a clearance hole for the roof mounting screw only slightly larger than the roof screw and small enough that the roofing washer can provide a nice seal against roofing material when tightened ie place roofing washer between roofing material and HDPE block see roof fixing details 7 When marking roof fixing points on U channel select the most suitable purlins ...

Страница 5: ...ible Here is an installation displaying a thermal break for hot and cold 4 way valve is inserted into hole drilled through inner baffle in cylinder 4 way valve usually takes the cold feed however in this example the cold feed is on the bottom left of image as this cylinder has two bottom ports ...

Страница 6: ...EVENLY SPREAD HEAT PAST AROUND TUBE TIP ROOF FIXING METHODS TOPHAT PURLIN ...

Страница 7: ...00mm then back up into the cylinder This prevents heat loss by heat drifting up the line This is particularly important for solar wetback installations and low pressure installations The circulation pump must be installed to draw the cooler water from the lower section of the cylinder and circulate this water through the collector before returning back to the cylinder at a point higher than the dr...

Страница 8: ...through the cap then insert the probe all the way into the horizontal thermocouple sleeve inside the cylinder Apply neutral cure sili cone just inside the outer casing of the cylinder under the cap then insert the cap Use tape to hold cable in place for minimum 24 hours to allow silicone to cure Once probes are secure clip cables using cable ties back to terminal box and trim excess cable to make ...

Страница 9: ...priority ie TH1 If only evening users of hot water set late afternoon heating back up as priority TH3 SETTING UP THE CONTROLLER Set Points are as per Owner Manual If there has been a power surge it is a good idea to check the controller to en sure settings have not reverted back to factory setting Ie if frost symbol has disappeared or T4 is not showing on screen when scrolling through parameters p...

Страница 10: ...ommended to have separate switching for elements independent of the controller otherwise an element can be accidently left on reducing the performance of the controller Please ensure the end user understands how the system is connected CAUTION Ripple or intermittent power can restrict use of intelligent time heating backup time heating and manual heating functions of controller For full user contr...

Страница 11: ...flooding through house not common This could happen where heat has got through to Polypropylene pipe and melted it Ensure that only copper is used where this can occur NB heat can travel up the cold supply pipe when the whole cylinder is HOT May require thermal trap on the cold supply bare copper pipe in a loop Check that the heat dump at the TPR valve can drain away without backing up and floodin...

Страница 12: ... when fill of water F Solar to be installed as to not compromise the structural integrity of the building G Please use appropriate fixings per roof type as contained in this manual for roof types outside of these then refer to Engineering manual otherwise specific engi neer design required and be certain that you do not use dissimilar metals that can cause corrosion H Controller manual and install...

Страница 13: ...Leading Solar Specialists Ice Solar Ltd 0064 3 3554323 gordon icesolar co nz View Our Online Store Scan to download manuals consent Scan to access www icesolar co nz Thank you for choosing Ice Solar ...

Отзывы: