FOR THE PLUMBER
CONFORM TO ALL APPLICABLE CODES
Water Supply:
The recommended water supply line is 3/8" O.D.
copper tubing, with a minimum operation pressure
of 20 PSIG, and a maximum of 80 PSIG. Connect
to cold water using the male flare connection at the
back of the machine. Install a shut off valve in an
accessible space between the ice maker and the
water supply.
Drain System:
All drains are of the gravity type, and must have a
minimum of 1/4" fall per foot of horizontal run. The
drains must be installed to conform to local
plumbing codes. The use of a vent at the machine
and at the bin will allow the system to drain
properly. Use only rigid tubing for drains; insulation
of the bin drain is recommended.
MFI2406LS
Page 5
SHUT OFF
VALVE
FIELD
SUPPLIED
WATER FILTER
3/8" MALE FLARE
3/4" FPT
VENT THIS DRAIN
WATER INLET
BIN DRAIN
FLOOR DRAIN
Содержание MFI2406LS Series
Страница 29: ...MFI Series Wiring Diagram 2406LS Page 27...