ELEVATION SERIES
REMOTE CONDENSER GUIDELINES
5
Route the refrigerant lines through the roof
opening. Follow straight line routing whenever
possible. Any excess tubing MUST remain with
the building. Spiral the excess length of pre-
charged tubing inside the building. Use a
horizontal spiral to avoid any traps in the lines.
Have the roofing contractor seal the holes in the
roof per local codes.
CAUTION: The couplings on the sets of pre-charged
lines are self sealing when installed properly.
Carefully follow the instructions in the Remote
Condenser manual
The following remote ice makers incorporate the Mixing Valve in the condenser. This configuration allows
up to a 100 foot calculated remote line set run. Reference the diagram on the next page to calculate the
maximum 100 ft. line set run. Maximum
actual line set run
is limited to 100 ft. Add 1/4 oz. of refrigerant
for each actual foot from 75 to 100 ft. actual line set run.
*Verify the CIM machine is compatible with the remote condenser.
For more information contact your Ice-O-Matic distributor
CIM Machine Model Number
Remote Condenser Model
Number
CIM0530R
VRC1001B/RCA1001
CIM0535R
VRC1061B/RCA1061
CIM0636R
VRC1061B/RCA1061
CIM1126R
VRC2061B/RCA1061
CIM0835R/836R/837R
VRC2061B/RCA1061
CIM1135R/1136R/1137R
VRC2061B/RCA1061