Applications
Typical Applications
•
Single zone
•
Single Ice Bear unit or multiple Ice Bear units
•
Partial storage system in a multi-stage configuration (displacing one or two stages of a multi-stage
system)
NOTE:
When applying an Ice Bear 30 unit to a heat pump, the Ice Bear unit must have a dedicated
(redundant) Ice-Coil.
Sample Ice Bear
®
Unit Configurations
•
Ice Bear unit (parallel) with Ice-Ready™ rooftop unit
•
Redundant (parallel) split system
Ice Bear
®
30 Unit (Parallel) with an Ice-Ready™ Rooftop Unit
The Ice Bear unit integrates with a modified packaged rooftop unit called an Ice-Ready rooftop unit. The
Ice-Ready rooftop unit, illustrated in the figure below, is a standard rooftop unit modified to include an
additional liquid overfeed coil (Ice-Coil™) that is dedicated to the Ice Bear unit. Specific systems are
available from name brand unit manufacturers as Ice-Ready rooftop units. For a list of currently
approved Ice-Ready rooftop units, and Ice-Coil kits, refer to the
Ice-Ready™ Products
Selection Guide
(Ice Energy form F091) or visit www.ice-energy.com. For other airside options, contact Ice Energy
Product Services (email [email protected] or call (877) 542-3232).
Figure 5 – Ice Bear
®
` 30 Unit (Parallel) with Ice-Ready™ Rooftop Unit
10 Ice
Bear
®
30 Unit Application Guide