Brushless Motor Driver SEH400RB

7.2ALARM RESET

If the above solutions don’t work, follow the operations below to reset the alarm signal

1.

MODE->P-05->SET

to check the alarm code, then press SET to reset the alarm.

2. Cut off the power supply, then power on again after 1 minute, the alarm can be released.

8 Troubleshooting

PhenomenonPossible reason

Troubleshooting

Motor stop

Alarm

Do as alarm code

Press Stop

Press Start

Wrongly motor lines

Check the wiring and phase

Motor brake is wrong

Make sure the motor brake is open

Driver doesn’t match the motor

This driver only supports motors with a Hall electrical

angle of 120°

Damage

Replace new motor and driver

Over heat

Over load

Make the load lower

Over current

Make the current lower

The ambient temperature is too high Improve environmental heat dissipation.
Wrong phase

Correct phase connection

Damage

Replace new motor and driver

Abnormal

motor speed

Overload

Make the load smaller

Signal input wrongly

Signal input checking

Wrong poles pairs numbers setting Set the right poles numbers
Wrong gear ratio setting

Set the right gear ratio

Wrong max speed setting

Set the maximum speed to the rated speed of the actual

motor

The motor is

running with

abnormal

noise

Phase wrongly

Check the motor phase

Driver doesn’t match the motor

This driver only supports motors with a Hall electrical

angle of 120°

Lack of phase wiring

Check the motor phase

Load problem

No load operation motor test

Motor problem

Change the motor

Motor speed

fluctuations

Signal input wrongly

Change to knob speed setting to check if there is the

same error

The load inertia ratio is too large

Decrease load inertia ratio or increase gear box

The load is changeable

Steady load or this condition is normal

No

signal

output

Pull-up resistor not connected

The alarm output interface and the speed output interface

are connected with appropriate pull-up resistors

Содержание SEH400RB

Страница 1: ...Brushless Motor Driver SEH400RB _________________________________________________________________...

Страница 2: ...iver port 3 4 2 Terminal Description 4 4 3 Description of external control signal circuit 4 4 4 Output circuit description 5 5 Introduction to panel functions 6 5 1Panel functions 6 5 2 Panel introduc...

Страница 3: ...ameters Adjustable speed with knob External potentiometer speed regulation Acceleration and deceleration time setting Pole pair setting Alarm display RS485 Rated speed accuracy as low as 0 5 2 Electri...

Страница 4: ...Brushless Motor Driver SEH400RB 3 Mechanical Dimensions Unit mm 4 Driver port and function description 4 1 Driver port...

Страница 5: ...tentiometer speed regulation EN If EN and GNDE connect the motor runs If EN and GNDE disconnect the motor stops They disconnect by default F R If F and GNDE connect the motor runs anti clockwise If F...

Страница 6: ...ternal potentiometer SV input wiring is shown below The external analog SV input wiring is shown below 4 4 Output circuit description ALM and SPD terminals as below its connection mode with PLC is rel...

Страница 7: ...tio setting Set the speed ratio of the reducer Alarm reset Display the alarm code and press SET to reset the alarm Polar number setting Set the pole pairs of the adaptive motor It is not recommended t...

Страница 8: ...Brushless Motor Driver SEH400RB 5 2 Panel introduction 5 3 Drive panel control settings...

Страница 9: ...Brushless Motor Driver SEH400RB Note All settings will be saved automatically immediately even power off without loss...

Страница 10: ...ee right 6 2 Direction control Here are two methods to control the direction 1 Through the panel MODE P 03 2 Disconnect F R and GNDE motor runs clockwise Connect F R and GNDE motor runs anti clockwise...

Страница 11: ...s to the GNDE port and the 5VE port respectively Refer to the picture below for details 2 External analog signal role DC 0 5V Note Be sure to set the correct number of motor pole pairs Relationship be...

Страница 12: ...shown in the figure below and three wires need to be connected B A GNDE The communication address can be set through the panel operation The 120 terminal matching resistance needs to be externally co...

Страница 13: ...0002 0X005F Speed Value 0 65535 0 RPM 0X0003 0X0066 Motor direction 0 4 1 0X0004 0X0068 Gear ratio 1 100 1 0X0005 0X0076 Alarm code 0 0X0006 0X0086 Pole pairs number 1 100 4 0X0007 0X0090 Under speed...

Страница 14: ...scription or note Speed adjusting modes selection 0 Knob speed regulation 1 External analog quantity 2 key or communication Speed setting The motor does not rotate when the set speed is lower than 400...

Страница 15: ...n the driver 2 Re match the motor and driver selection 3 Replace the driver AL05 Hall error 1 Check whether the motor sensor cable is firmly connected 2 Check whether the Hall element in the motor is...

Страница 16: ...on Damage Replace new motor and driver Abnormal motor speed Overload Make the load smaller Signal input wrongly Signal input checking Wrong poles pairs numbers setting Set the right poles numbers Wron...

Страница 17: ...t or electric parameters that does not meet the use parameters is not covered by the warranty Product damage caused by improper selection is not covered by the warranty Product damage caused by unauth...

Отзывы: