On first launch, the installation and pump must be carefully deaerated. When the 
pump is deaerated, the level of the noise generated by the device motor drops. 

Observe the following limitations: 

Heating medium 
temperature [

O

C] 

Minimal  inflow  pressure  on  the 
suction side [bar] / [m] / [Pa] 

≤ 75 

0.05 bar / 0.5 m / 5 000 Pa 

90 

0.28 bar / 2.8 m / 28 000 Pa 

110 

1.08 bar / 10.8 m / 108 000 Pa 

 

When the surrounding temperature and heating medium temperature ratio is 
incorrect, it can result in water steam condensation in the terminal box and 
motor stator. In order to avoid it, it is essential to observe the following rule 
at  all  times:  the  temperature  of  heating  agent  must  be  higher  than  the 
temperature  of  surroundings.  Minimal  temperature  of  heating  medium  is 
2

O

C. 

The  temperature  of  surroundings  cannot  exceed  30

O

C,  and  the  maximum 

temperature of heating medium is 110

O

C. When the temperature of surroundings is 

40

O

C,  the  temperature  of  heating  medium  cannot  exceed  70

O

C.  For  35

O

C  of 

surroundings, the max. temp. of medium is 90

O

C. 

Device  destruction  as  a  result  of  water  steam  condensation  is  not  subject  to 
warranty repair. 

The  temperature  of  pump  surface  can  never  exceed  120

O

C.  Device 

destruction as a result of installation overheating is not subject to warranty 
repair. 

PUMP DISPOSAL: 

 

 

The used product is subject to disposal as wastes only in selective waste 
collection systems organised by the Network of Communal Electric and 
Electronic Waste Collection Centres. The customer is entitled to return 
the used equipment to the network of the electric equipment distributor, 
at least for free and directly, if the returned device is of proper type and 
fulfils the same function as a newly purchased device. It is prohibited to 
dispose of electric equipment together with other household wastes. 

Failure-free  pump  operation  requires  minimal  inflow  pressure  of  heating 
medium (water) on the suction side of the pump. The minimal inflow pressure 
depends on the heating medium temperature. The higher the temperature, the 
higher inflow pressure must be provided on the suction side of the pump. 

 

Содержание BETA

Страница 1: ...arising from potential device failure caused by the use that is inconsistent with instructions of its use NOTE failure to observe the instructions included in the manual can result in hazard for persons properties in which they are installed environment and the pump itself CAUTION This equipment is not intended for use by persons including children with reduced motor sensory or mental capacities o...

Страница 2: ...pumping of clean water with no solid or abrasive particles Pumping water containing mechanical contamination results in fast wear and tear of the pump and in consequence it its failure In such a case only paid repair is available The pump is not adjusted to pump caustic flammable destructive or explosive substances e g petrol nitro oil etc foodstuffs or salty water Failure caused by pumping of the...

Страница 3: ...bottom This type of installation protects against water penetration into the cable box in case of leakage in the water installation Device destruction caused by pouring water into the terminal box from the outside is not subject to warranty repair Despite the possibility of pump operation in water pumping in a vertical downward direction the manufacturer recommends the installation which makes it ...

Страница 4: ...uipped with a residual current device with rated making current In not exceeding 30 mA The manufacturer and guarantor are not liable for any damage to people or property resulting from supplying the pump with power without a proper switch PUMP OPERATION CONTROL Upon launch of the pump the display of the power consumption meter will show the current power consumption of the pump When the message tw...

Страница 5: ...rameters of pump operation depending on the selected operation mode are presented in the diagram example diagram for pump BETA 25 60 RECOMMENDED SETPOINTS DEPENDING ON THE TYPE OF CENTRAL HEATING CO INSTALLATION 1 If there is a two pipe central heating installation routed in the house i e one pipe serves as the supply line for all heaters in the loop and the other in parallel position is used only...

Страница 6: ...rate with a pump operating in a night mode The principle of NIGHT MODE operation The use of the night mode switch will cause the automatic system of the pump will monitor the temperature changes in flowing water If the temperature signalling unit detects temperature lowering of at least 0 1 O C min in the period of about 2 hours it will result in automatic switch the pump into night operation mode...

Страница 7: ...not exceed 70O C For 35O C of surroundings the max temp of medium is 90O C Device destruction as a result of water steam condensation is not subject to warranty repair The temperature of pump surface can never exceed 120O C Device destruction as a result of installation overheating is not subject to warranty repair PUMP DISPOSAL The used product is subject to disposal as wastes only in selective w...

Страница 8: ...to the installation Check the amount of air in the collecting container Pump capacity is too high Decrease pressure on the suction side of the device Pump is operating but installation fails to supply enough heat Panel displays a number Too low pump operation parameters Increase pressure on the suction side of the device Switch the pump setpoint into a higher operation mode EC DECLARATION OF CONFO...

Отзывы: