Power Systems

Servicing the IBM Power System IC922

(9183-22X)

IBM

Содержание Power System IC922

Страница 1: ...Power Systems Servicing the IBM Power System IC922 9183 22X IBM...

Страница 2: ...ual G229 9054 and the IBM Environmental Notices and User Guide Z125 5823 This edition applies to IBM Power Systems servers that contain the POWER9 processor and to all associated models Copyright Inte...

Страница 3: ...tribution board 63 Power supplies 66 Removing a power supply 66 Replacing a power supply 69 Power switch and cables 70 Removing the power switch and cables 70 Replacing the power switch and cables 74...

Страница 4: ...status 156 Removing and replacing covers 156 Removing the service access cover 156 Installing the service access cover 157 Service and operating positions 158 Placing the system into the service posi...

Страница 5: ...1 800 300 8751 German safety information Das Produkt ist nicht f r den Einsatz an Bildschirmarbeitspl tzen im Sinne 2 der Bildschirmarbeitsverordnung geeignet Laser safety information IBM servers can...

Страница 6: ...nect 1 Turn off everything unless instructed otherwise 2 For AC power remove the power cords from the outlets 3 For racks with a DC power distribution panel PDP turn off the circuit breakers located i...

Страница 7: ...devices that attach to the system It is the responsibility of the customer to ensure that the outlet is correctly wired and grounded to prevent an electrical shock R001 part 1 of 2 R001 part 2 of 2 CA...

Страница 8: ...that the route that you choose can support the weight of the loaded rack cabinet Refer to the documentation that comes with your rack cabinet for the weight of a loaded rack cabinet Verify that all d...

Страница 9: ...position for example when working from a ladder Stability hazard The rack may tip over causing serious personal injury Before extending the rack to the installation position read the installation ins...

Страница 10: ...e equipped with multiple AC power cords or multiple DC power cables To remove all hazardous voltages disconnect all power cords and power cables L003 L007 CAUTION A hot surface nearby L007 x Power Sys...

Страница 11: ...ing into the other end of a disconnected optical fiber to verify the continuity of optic fibers may not injure the eye this procedure is potentially dangerous Therefore verifying the continuity of opt...

Страница 12: ...th platforms without appreciable force so take care not to push or lean Keep riser tilt adjustable angling platform option flat at all times except for final minor angle adjustment when needed Do not...

Страница 13: ...itable for connection to intrabuilding or unexposed wiring or cabling only The intrabuilding ports of this equipment must not be metallically connected to the interfaces that connect to the OSP outsid...

Страница 14: ...xiv Power Systems Servicing the IBM Power System IC922 9183 22X...

Страница 15: ...ther product Do not open or service any power supply assembly Do not connect or disconnect any cables or perform installation maintenance or reconfiguration of this product during an electrical storm...

Страница 16: ...the circuit breakers located in the PDP 6 Turn on the devices Sharp edges corners and joints may be present in and around the system Use care when handling equipment to avoid cuts scrapes and pinchin...

Страница 17: ...ist strap follow all electrical safety procedures An ESD wrist strap is used for static control It does not increase or decrease your risk of receiving electric shock when using or working on electric...

Страница 18: ...he front drive cables and power cables Press the cable connector latchs and disconnect the front drive cables and the power cable from the drive backplane as shown in the following figure Be sure to u...

Страница 19: ...he drive backplane 5 Unscrew the two captive thumbscrews A of the drive backplane until fully loose as shown in the following figure If needed use a Phillips 2 screwdriver to loosen the screws Removin...

Страница 20: ...ischarge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Align and place the drive backplane into the system Insert...

Страница 21: ...ng the drive backplane 4 Using your labels connect the power cables and front drive cables as shown in the following figure Push the connectors in until the latches click Removing and replacing parts...

Страница 22: ...e drive backplane 5 Fully seat all the front drives into their slots as shown in the following figure Push drive lever A until the front drive is seated and the lever snaps closed 8 Power Systems Serv...

Страница 23: ...ng the 9183 22X system for operation after you remove and replace internal parts on page 150 Removing and replacing a hard disk drive or solid state drive in the 9183 22X system Learn how to remove an...

Страница 24: ...uct from ESD packaging and installing or replacing hardware touch an unpainted metal surface of the system for a minimum of 5 seconds If at any point in this service process you move away from the sys...

Страница 25: ...as you slide it out of the system Do not hold the drive by the handle 5 If you are removing more than one drive repeat the steps in this procedure until all drives are removed Replacing a front hard d...

Страница 26: ...kup media Removing and replacing fans in the 9183 22X system Find information about removing and replacing fans in the IBM Power System IC922 9183 22X server Removing and replacing a fan in the 9183 2...

Страница 27: ...ting when shorted with metal which might result in splattered metal burns or both L005 L008 CAUTION Hazardous moving parts nearby L008 Procedure 1 Loosen the cover screw B at the rear of the system as...

Страница 28: ...r instructions see Placing a 9183 22X system into the service position on page 159 CAUTION Do not place any object on top of a rack mounted device unless that rack mounted device is intended for use a...

Страница 29: ...increase or decrease your risk of receiving electric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and...

Страница 30: ...ft the fan from the system as shown in the following figure Attention When the system is powered on a fan can be unplugged for only 20 seconds before the system shuts down Once you unplug a fan you ha...

Страница 31: ...replace a fan lower the fan into the system and align the fan with the slots in the fan cage assembly as shown in the following figure Press the fan down until it snaps into place Removing and replac...

Страница 32: ...the cover A on the system unit such that the alignment pins on the cover are aligned to the slots on the chassis Slide the cover to the front of the system until the blue release latches B lock in to...

Страница 33: ...Installing the cover 8 Place the system into the operating position For instructions see Placing a 9183 22X system into the operating position on page 160 L012 Removing and replacing parts in the 918...

Страница 34: ...cage assembly from the 9183 22X system To remove the fan cage assembly from the system complete the steps in this procedure Before you begin Power off the system and place it in the service position F...

Страница 35: ...ures An ESD wrist strap is used for static control It does not increase or decrease your risk of receiving electric shock when using or working on electrical equipment If you do not have an ESD wrist...

Страница 36: ...charge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Lower the fan cage assembly into the system and align the fa...

Страница 37: ...ormation about removing and replacing memory modules in the IBM Power System IC922 9183 22X server Removing and replacing memory modules from the 9183 22X system To remove and replace a memory module...

Страница 38: ...dures An ESD wrist strap is used for static control It does not increase or decrease your risk of receiving electric shock when using or working on electrical equipment If you do not have an ESD wrist...

Страница 39: ...he air baffle Remove 3 Locate the memory module to remove The following figure shows the location of the memory modules in the system Figure 18 Locating the memory modules Removing and replacing parts...

Страница 40: ...shown in the following figure Figure 19 Retracting the retaining pin and removing the left cable holder c Lift the drive cable holder out of the system 5 If the memory socket is covered by a PCIe ris...

Страница 41: ...on the right side of the system complete the following steps to remove the power distribution board Removing the power distribution board requires that the power supplies be partially removed from th...

Страница 42: ...out of the system d Remove the cables from the top of the power distribution board e To remove the power distribution board unlatch tab A unplug and lift the power distribution board from the system b...

Страница 43: ...odule from the slot a Unlock the memory module by pushing the locking tabs away from the memory module in the direction shown in the following figure The lever action of opening the tabs pushes the me...

Страница 44: ...f the slot 8 Place the memory module on an ESD mat Replace 9 To replace a memory module complete the following steps a Push the locking tabs to the open position away from the slot in the direction sh...

Страница 45: ...ress firmly on each side of the memory module until the locking tab locks in place with an audible click 10 If you removed a PCIe riser replace the PCIe riser by using the following procedure a Move t...

Страница 46: ...m replace the holder by using the following procedure a Replace the drive cable holder in the system Ensure that the alignment pins match the slots in the holder b Reset the retaining pin A to lock th...

Страница 47: ...ace the power distribution board by using the following procedure a Replace the power distribution board by plugging it into the system backplane as shown in the following figure Use the alignment pin...

Страница 48: ...he power distribution board a Replace the drive cable holder in the system Ensure that the alignment pins match the slots in the holder b Reset the retaining pin A to lock the holder in place as shown...

Страница 49: ...ce the drive cables into the drive cable holder 13 Replace the air baffle A straight down into the chassis as shown in the following figure Ensure that the pins inside the system side walls align prop...

Страница 50: ...the system The considerations for installing memory modules in the system follow The system supports up to 32 DDR4 RDIMM memory modules The system supports memory module sizes 16 GB 32 GB and 64 GB fo...

Страница 51: ...ystem The following figure shows the locations for memory modules in the 9183 22X system Figure 30 Memory module slot locations The following table shows the order in which memory modules must be plac...

Страница 52: ...22X system to remove and replace internal parts on page 146 Note If a CacheVault power module is attached to the adapter remove the CacheVault power module and cable For details see the Broadcom web s...

Страница 53: ...n discharge yourself by touching an unpainted metal surface for at least 5 seconds before you continue with the service process 2 Lift the air baffle A straight up as shown in the following figure Pla...

Страница 54: ...he cable connector latch and disconnect the front drive cable from the drive backplane as shown in the following figure Be sure to unlatch the cable from the connectors Do not pull in the cables thems...

Страница 55: ...rew using a Phillips 1 screwdriver and lift the PCIe adapter from the system backplane as shown in the following figure b If needed label and remove any plugs or cables that extend out from the rear o...

Страница 56: ...from a PCIe riser complete the following steps a Label the PCIe riser b Remove the drive cables from the drive cable holders along the sides of the system c Lift the PCIe riser up out of the system as...

Страница 57: ...unplug the cables by using the connector e If needed label and remove the cables from the PCIe adapter Press the cable connector latch to unlatch the cable Do not pull in the cables themselves unplug...

Страница 58: ...u remove parts from the system you must ensure that PCIe tailstock fillers are present System airflow baffle is present Notes If you are installing or replacing a Broadcom 93xx adapter FC EK41 FC EK43...

Страница 59: ...labels insert the cables into the PCIe adapter Push the connector in until the latch clicks b Align the adapter properly and insert it fully into the slot as shown in the following figure c Replace th...

Страница 60: ...apter into the PCIe riser d Using your labels replace any plugs or cables that extend out from the rear of the PCIe adapter e Insert the PCIe riser into the system backplane as shown in the following...

Страница 61: ...long the sides of the system 5 If you disconnected the drive cables complete the following steps a Using your labels reconnect the front drive cables to the drive backplanes as shown in the following...

Страница 62: ...age assembly into the system and align the fan cage assembly with the slots in the chassis Simultaneously rotate the two latches at A down as shown in the following figure until the fan cage assembly...

Страница 63: ...bly 6 Replace the air baffle A straight down into the chassis as shown in the following figure Ensure that the pins inside the system side walls align properly with the slots in the cover B Removing a...

Страница 64: ...ind information about removing and replacing PCIe risers in the IBM Power System IC922 9183 22X server Removing a PCIe riser from the 9183 22X system To remove a PCIe riser from the system complete th...

Страница 65: ...safety procedures An ESD wrist strap is used for static control It does not increase or decrease your risk of receiving electric shock when using or working on electrical equipment If you do not have...

Страница 66: ...figure Lift the fan cage assembly from the system Figure 44 Removing the fan cage assembly c Disconnect the front drive cables from the drive backplane Press the cable connector latch and disconnect...

Страница 67: ...iser from the system complete the following steps a Label the PCIe riser b Remove the drive cables from the drive cable holders along the sides of the system c Lift the PCIe riser up out of the system...

Страница 68: ...lug the cables by using the connector 5 To remove a PCIe adapter from a PCIe riser complete the following steps a Label the PCIe adapter to note the position of the adapter in the riser b If needed la...

Страница 69: ...1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 To replace a PC...

Страница 70: ...ce any plugs or cables that extend out from the rear of the PCIe adapter f Insert the PCIe riser into the system backplane as shown in the following figure Insert the riser by using the slots and alig...

Страница 71: ...long the sides of the system 3 If you disconnected the drive cables complete the following steps a Using your labels reconnect the front drive cables to the drive backplanes as shown in the following...

Страница 72: ...age assembly into the system and align the fan cage assembly with the slots in the chassis Simultaneously rotate the two latches at A down as shown in the following figure until the fan cage assembly...

Страница 73: ...bly 4 Replace the air baffle A straight down into the chassis as shown in the following figure Ensure that the pins inside the system side walls align properly with the slots in the cover B Removing a...

Страница 74: ...about removing and replacing the power distribution board in the IBM Power System IC922 9183 22X server Removing the power distribution board from the 9183 22X system To remove the power distribution...

Страница 75: ...orking on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an unpainted metal surface of the...

Страница 76: ...out of the system 4 Remove the cables from the top of the power distribution board 5 To remove the power distribution board unlatch tab A unplug and lift the power distribution board from the system b...

Страница 77: ...p on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 If present reconnect the power cables to the front of the power distribution boar...

Страница 78: ...able holder on the right side of the system by using the following procedure a Replace the drive cable holder in the system Ensure that the alignment pins match the slots in the holder b Reset the ret...

Страница 79: ...ce the drive cables into the drive cable holder 6 Replace the air baffle A straight down into the chassis as shown in the following figure Ensure that the pins inside the system side walls align prope...

Страница 80: ...n the 9183 22X system Find information about removing and replacing power supplies in the IBM Power System IC922 9183 22X server Removing a power supply from the 9183 22X system To remove a power supp...

Страница 81: ...when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an unpainted metal...

Страница 82: ...product might be equipped with multiple AC power cords or multiple DC power cables To remove all hazardous voltages disconnect all power cords and power cables L003 L005 68 Power Systems Servicing th...

Страница 83: ...3 c on page 69 for the other power supply Figure 59 Removing the power supplies from the system Replacing a power supply in the 9183 22X system To replace a power supply in the system complete the st...

Страница 84: ...er System IC922 9183 22X system About this task The power switch includes the front USB port Removing the power switch and cables from the 9183 22X system To remove the power switch and cables complet...

Страница 85: ...lectric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an un...

Страница 86: ...B from the system backplane as shown in the following figure Feed the power switch cable and the USB cable through the opening in the side of the chassis as shown in the following figure If needed mo...

Страница 87: ...gure 63 Disconnecting the power switch and front USB cables 5 Remove the two screws A and B that secure the power switch as shown in the following figure Removing and replacing parts in the 9183 22X 7...

Страница 88: ...Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Faste...

Страница 89: ...le and the USB cable through the opening in the side of the chassis as shown in the following figure Connect the power switch cable A and the front USB cable B to the system backplane as shown in the...

Страница 90: ...the power switch and front USB cables against the outside of the system b Put the side channel back into place covering the cables Ensure the tab at A is inserted into the slot c Secure the side chann...

Страница 91: ...l 5 Replace the air baffle A straight down into the chassis as shown in the following figure Ensure that the pins inside the system side walls align properly with the slots in the cover B Removing and...

Страница 92: ...e system backplane in the IBM Power System IC922 9183 22X server Preparing the 9183 22X system to remove the system backplane To prepare the system to remove a system backplane complete the steps in t...

Страница 93: ...s not increase or decrease your risk of receiving electric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packagi...

Страница 94: ...lder out of the system 4 Remove the drive cable holder on the right side of the system by using the following procedure a Remove the drive cables from the drive cable holder b Retract the retaining pi...

Страница 95: ...lane replacement procedure This process keeps the parts safe during the system backplane replacement As part of the system processor module replacement the heat sink is removed If the system processor...

Страница 96: ...22X system on page 70 5 Label and remove the PCIe adapters and PCIe risers from the system backplane and set them on an ESD surface For instructions see Removing a PCIe adapter from the 9183 22X syste...

Страница 97: ...Figure 72 Removing the system backplane b Using the two blue touch points B slide the system backplane forwards about 6 cm 25 in Removing and replacing parts in the 9183 22X 83...

Страница 98: ...arge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Remove the replacement system backplane from the static protec...

Страница 99: ...Figure 73 Replacing the system backplane 4 Replace the 3 screws A to secure the system backplane to the system Removing and replacing parts in the 9183 22X 85...

Страница 100: ...emove the heat sink by lifting it upward Set the heat sink aside with the module side face up Note If you plan to remove dust or debris from the heat sink this operation must be completed in another r...

Страница 101: ...present use the supplied air pump to clean the system processor module area Blow small bursts of air from the center toward the sides of the system processor module as shown in the following figure I...

Страница 102: ...cover from a system processor socket 10 Prepare the system processor module for removal a Open the latches that hold the system processor module in the supplied removal tool A Push down on the ring B...

Страница 103: ...l tool latches b Lower the tool over the system processor module while ensuring that the two guide pins A insert into the alignment holes B on each side of the tool See the following figure Removing a...

Страница 104: ...p of the system processor module push down on the ring A to close the latches C and lock the system processor module into the tool Make sure that both of the tool jaws are locked on the system process...

Страница 105: ...backplane socket 12 Remove the dust covers from the system processor module sockets on the new system backplane 13 Install the system processor module a If dust or debris is present on the system proc...

Страница 106: ...r the tool evenly without tilting the tool See the following figure Note Do not attempt to slide the tool and the system processor module in any direction while the system processor module is touching...

Страница 107: ...rocessor module c Open the latches that hold the system processor module in the supplied removal tool A Push down on the ring B while pressing in on the tabs C See the following figure Removing and re...

Страница 108: ...he system processor module 14 Inspect the thermal interface material TIM for visible signs of damage as shown in the following figure If you see folds tears bends or if you have doubts about the TIM r...

Страница 109: ...reuse the existing heat sink a Open the TIM packaging and carefully remove the TIM holding it by the edges of the carrier strip and holding it away from the shipping container b Remove the protective...

Страница 110: ...Figure 84 Installing a new TIM onto the system processor module d Place the heat sink on the TIM as shown in the following figure 96 Power Systems Servicing the IBM Power System IC922 9183 22X...

Страница 111: ...ing undamaged TIM and heat sink a Using the tweezers move the old TIM from the clean dry surface and center it onto the new system processor module The TIM has no preferred up side The TIM can be plac...

Страница 112: ...Figure 86 Replacing the TIM onto the system processor module b Place the heat sink on the TIM as shown in the following figure 98 Power Systems Servicing the IBM Power System IC922 9183 22X...

Страница 113: ...load arms are engaged as shown by A in the following figure b Tighten the center load screw clockwise by using the supplied hex key as shown by B in the following figure until a firm stop is reached...

Страница 114: ...system backplane to the new system backplane For instructions see Removing and replacing the time of day battery in the 9183 22X system on page 128 24 Transfer the memory modules from the old system b...

Страница 115: ...ce the drive cable holder on the right side of the system by using the following procedure a Replace the drive cable holder in the system Ensure that the alignment pins match the slots in the holder b...

Страница 116: ...assembly in the system For instructions see Replacing the fan cage assembly in the 9183 22X system on page 22 Preparing the system for operation after replacing the system backplane in the 9183 22X s...

Страница 117: ...product power scale out_lc b In the search field enter your machine type and model Then click the correct product support entry for your system c From the Downloads list click Scale out LC system VPD...

Страница 118: ...d heat sink on hand Procedure 1 Attach the electrostatic discharge ESD wrist strap The ESD wrist strap must be connected to an unpainted metal surface until the service procedure is completed and if a...

Страница 119: ...e 92 Opening the system processor module packaging 3 Lift the air baffle A straight up as shown in the following figure Place the air baffle on a clean area Removing and replacing parts in the 9183 22...

Страница 120: ...ves freely See the following figure b Hold the heat sink B on opposing sides and remove the heat sink by lifting it upward Set the heat sink aside with the module side face up Note If you plan to remo...

Страница 121: ...ink 5 Using tweezers carefully remove the TIM from the top of the system processor module and place it in a clean dry area as shown in the following figure The TIM can tear easily Removing and replaci...

Страница 122: ...use the supplied air pump to clean the system processor module area Blow small bursts of air from the center toward the sides of the system processor module as shown in the following figure If your a...

Страница 123: ...ea 7 Prepare the system processor module for removal a Open the latches that hold the system processor module in the supplied removal tool A Push down on the ring B while pressing in on the tabs C See...

Страница 124: ...atches b Lower the tool over the system processor module while ensuring that the two guide pins A insert into the alignment holes B on each side of the tool See the following figure 110 Power Systems...

Страница 125: ...l on top of the system processor module push down on the ring A to close the latches C and lock the system processor module into the tool Make sure that both of the tool jaws are locked on the system...

Страница 126: ...e them at an angle in the top cover of the system processor module packaging as shown in the following figure Note Set the tool and system processor module at an angle on the top cover of the system p...

Страница 127: ...top cover of the packaging 9 Open the latches that hold the system processor module in the supplied removal tool A Push down on the ring B while pressing in on the tabs C See the following figure Rem...

Страница 128: ...ound jack or connected to an unpainted metal surface If not do so now 2 Remove dust and debris from the system processor socket area If dust or debris is present use the supplied air pump to clean the...

Страница 129: ...l tool latches b Lower the tool over the system processor module while ensuring that the two guide pins A insert into the alignment holes B on each side of the tool See the following figure Removing a...

Страница 130: ...p of the system processor module push down on the ring A to close the latches C and lock the system processor module into the tool Make sure that both of the tool jaws are locked on the system process...

Страница 131: ...tool out of the system processor module tray 5 Install the system processor module a If dust or debris is present on the system processor socket use the supplied air pump to clean the socket Blow sma...

Страница 132: ...r the tool evenly without tilting the tool See the following figure Note Do not attempt to slide the tool and the system processor module in any direction while the system processor module is touching...

Страница 133: ...rocessor module c Open the latches that hold the system processor module in the supplied removal tool A Push down on the ring B while pressing in on the tabs C See the following figure Removing and re...

Страница 134: ...the system processor module 6 Inspect the thermal interface material TIM for visible signs of damage as shown in the following figure If you see folds tears bends or if you have doubts about the TIM r...

Страница 135: ...g heat sink a Open the TIM packaging and carefully remove the TIM holding it by the edges of the carrier strip and holding it away from the shipping container b Remove the protective film from the cle...

Страница 136: ...Figure 109 Installing a new TIM onto the system processor module d Place the heat sink on the TIM as shown in the following figure 122 Power Systems Servicing the IBM Power System IC922 9183 22X...

Страница 137: ...ing undamaged TIM and heat sink a Using the tweezers move the old TIM from the clean dry surface and center it onto the new system processor module The TIM has no preferred up side The TIM can be plac...

Страница 138: ...Figure 111 Replacing the TIM onto the system processor module b Place the heat sink on the TIM as shown in the following figure 124 Power Systems Servicing the IBM Power System IC922 9183 22X...

Страница 139: ...ngaged as shown by A in the following figure b Tighten the center load screw clockwise by using the supplied hex key as shown by B in the following figure until a firm stop is reached If the heat sink...

Страница 140: ...sink 11 Replace the air baffle A straight down into the chassis as shown in the following figure Ensure that the pins inside the system side walls align properly with the slots in the cover B 126 Powe...

Страница 141: ...you replaced by the edges Lift it off the packaging cover Align the beveled corner of the module A to the corner of the packaging with triangle B and place it in the packaging as shown in the followi...

Страница 142: ...tery complete the steps in this procedure Before you begin Power off the system and place it in the service position For instructions see Preparing the 9183 22X system to remove and replace internal p...

Страница 143: ...the system it is important to again discharge yourself by touching an unpainted metal surface for at least 5 seconds before you continue with the service process 2 Lift the air baffle A straight up a...

Страница 144: ...lot on the system backplane as shown in the following figure Insert the bottom of the battery into bottom of the holder then rotate the battery into the holder Ensure to insert the battery with the co...

Страница 145: ...system backplane 5 Replace the air baffle A straight down into the chassis as shown in the following figure Ensure that the pins inside the system side walls align properly with the slots in the cover...

Страница 146: ...about removing and replacing the trusted platform module TPM card in the IBM Power System IC922 9183 22X server Removing the trusted platform module card from the 9183 22X system To remove a trusted...

Страница 147: ...rking on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an unpainted metal surface of the s...

Страница 148: ...lder c Lift the drive cable holder out of the system 4 To remove the TPM card pull the lever A to release the TPM card Lift the TPM card straight up from the system backplane as shown in the following...

Страница 149: ...that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 To replace the TPM card a...

Страница 150: ...em by using the following procedure a Replace the drive cable holder in the system Ensure that the alignment pins match the slots in the holder b Reset the retaining pin A to lock the holder in place...

Страница 151: ...ce the drive cables into the drive cable holder 4 Replace the air baffle A straight down into the chassis as shown in the following figure Ensure that the pins inside the system side walls align prope...

Страница 152: ...What to do next Prepare the system for operation For instructions see Preparing the 9183 22X system for operation after you remove and replace internal parts on page 150 138 Power Systems Servicing t...

Страница 153: ...AC power disconnect all power cords from their AC power source For racks with a DC power distribution panel PDP disconnect the customer s DC power source to the PDP When connecting power to the produc...

Страница 154: ...2 DANGER Observe the following precautions when working on or around your IT rack system Heavy equipment personal injury or equipment damage might result if mishandled Always lower the leveling pads...

Страница 155: ...air flow is compromised Ensure that air flow is not blocked or reduced on any side front or back of a unit used for air flow through the unit Consideration should be given to the connection of the equ...

Страница 156: ...e product might be equipped with multiple AC power cords or multiple DC power cables To remove all hazardous voltages disconnect all power cords and power cables L003 L005 142 Power Systems Servicing...

Страница 157: ...ovider of your parts or next level of support If you are installing a feature contact one of the following service organizations The provider of your parts or next level of support In the United State...

Страница 158: ...constant green light indicates that the drive is present a flashing green light indicates activity An amber light indicates a problem On the power supplies a constant green light indicates that the sy...

Страница 159: ...to turn on the blue identify LED to help you find the system that needs servicing Procedure You can activate the blue system identify LED by pressing the Identify LED button on the control panel for a...

Страница 160: ...ntifying the system that contains the part to replace on page 143 3 Attach the electrostatic discharge ESD wrist strap The ESD wrist strap must be connected to an unpainted metal surface until the ser...

Страница 161: ...em on page 153 5 Disconnect the power source from the system by unplugging the system For instructions see Disconnecting power cords from the 9183 22X system on page 161 Note The system might be equip...

Страница 162: ...attered metal burns or both L005 6 If the power distribution board needs to be removed if the system backplane needs to be removed or if DIMM 0 needs to be installed removed or replaced partially remo...

Страница 163: ...tions see Placing a 9183 22X system into the service position on page 159 CAUTION Do not place any object on top of a rack mounted device unless that rack mounted device is intended for use as a shelf...

Страница 164: ...ectrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Replace the service access cover For instruct...

Страница 165: ...Restart the system For instructions see Starting the 9183 22X system on page 152 8 If you installed or replaced a PCIe adapter update the adapter firmware See Getting firmware fixes for vendor I O ada...

Страница 166: ...d verify the following items All system power cables are connected to a power source The power on LED as shown in the following figure is flashing A flashing light indicates standby power to the unit...

Страница 167: ...s the system to shut down and then power off The indicates the time in minutes before the shutdown occurs Drive commands for the 9183 22X system Learn about the storage drive commands for the system S...

Страница 168: ...orce storcli cx set bios state on off Mode SOE PE IE SME abs on off DeviceExposure value storcli cx show bios storcli cx show safeid storcli cx show rehostinfo storcli cx show ASO storcli cx add vd r...

Страница 169: ...set config file fileName storcli cx cv show storcli cx cv show all storcli cx px show storcli cx px show all To show a summary of the drive and controller status storcli show To show a list of all co...

Страница 170: ...v Sensors that have a status of present and functional do not require a service action Sensors that have a status of present and not functional require a service action Some occurrences of errors in...

Страница 171: ...e cover before you power on the system Figure 135 Removing the cover Installing the service access cover on a 9183 22X system To replace the service access cover complete the steps in this procedure A...

Страница 172: ...tem until the blue release latches B lock in to place Figure 136 Installing the cover 2 Fasten the cover screw C at the rear of the cover Service and operating positions for the 9183 22X system Find i...

Страница 173: ...les at the rear of the system unit do not catch or bind as you pull the system unit forward in the rack When the slide rails are fully extended the rail safety latches lock into place This action prev...

Страница 174: ...m in the operating position ensure that the cables at the rear of the system do not catch or bind as you push the system unit back into the rack Procedure 1 Press in the rail safety latches A on both...

Страница 175: ...nfasten the hook and loop fasteners that tie the power cords to the power supply handle Note how the power is looped you need to make that same loop when you reattach the power cords Figure 139 Routin...

Страница 176: ...o connect a power cord complete the steps in this procedure Procedure 1 Open the rear rack door on the system unit that you are servicing 2 Using your labels reconnect the power cords to the system un...

Страница 177: ...oped be sure to maintain at least a 5 cm 2 in diameter loop Use the hook and loop fastener to tie the power cord to the power supply handle Figure 142 Routing the power cord loop in the cable manageme...

Страница 178: ...164 Power Systems Servicing the IBM Power System IC922 9183 22X...

Страница 179: ...duct s and or the program s described in this publication at any time without notice Any references in this information to non IBM websites are provided for convenience only and do not in any manner s...

Страница 180: ...information technology content successfully Overview The IBM Power Systems servers include the following major accessibility features Keyboard only operation Operations that use a screen reader The IB...

Страница 181: ...rovide you as the customer the ability to collect personally identifiable information from end users via cookies and other technologies you should seek your own legal advice about any laws applicable...

Страница 182: ...ngen der EU Richtlinie 2014 30 EU zur Angleichung der Rechtsvorschriften ber die elektromagnetische Vertr glichkeit in den EU Mitgliedsstaatenund h lt die Grenzwerte der EN 55022 EN 55032 Klasse A ein...

Страница 183: ...elle Informationen Das Ger t erf llt die Schutzanforderungen nach EN 55024 und EN 55022 EN 55032 Klasse A Japan Electronics and Information Technology Industries Association JEITA Notice This statemen...

Страница 184: ...radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area...

Страница 185: ...luding the fitting of non IBM option cards German Notice Deutschsprachiger EU Hinweis Hinweis f r Ger te der Klasse B EU Richtlinie zur Elektromagnetischen Vertr glichkeit Dieses Produkt entspricht de...

Страница 186: ...Schutzanforderungen nach EN 55024 und EN 55032 Klasse B Japan Electronics and Information Technology Industries Association JEITA Notice This statement applies to products less than or equal to 20 A p...

Страница 187: ...or television interference caused by using other than recommended cables and connectors or by unauthorized changes or modifications to this equipment Unauthorized changes or modifications could void...

Страница 188: ...ermined by IBM the above instructions are not being properly followed You may not download export or re export this information except in full compliance with all applicable laws and regulations inclu...

Страница 189: ......

Страница 190: ...IBM...